Page 257 - 2018_IFC
P. 257

ENERGY SYSTEMS



           other storage batteries and other safety systems. Introduc-    room separation specified in Table 509 of the
           ing other types of storage batteries into the stationary stor-  International Building Code.
           age battery system or other types of electrolytes into flow  1206.2.8.4 Separate rooms. Where stationary batteries
           battery systems shall be treated as a new installation and  are installed in a separate equipment room that can be
           require approval by the  fire code  official before the  accessed only by authorized personnel, they shall be
           replacements are introduced into service.
                                                                   permitted to be installed on an open rack for ease of
           1206.2.8 Location and construction.  Rooms and areas    maintenance.
           containing stationary storage battery systems shall be
           designed, located and constructed in accordance with Sec-  1206.2.8.5 Occupied work centers. Where stationary
           tions 1206.2.8.1 through 1206.2.8.7.4.                  storage batteries are located in an occupied work cen-
                                                                   ter, they shall be housed in a noncombustible cabinet or
              1206.2.8.1 Location. Stationary storage battery sys-  other enclosure to prevent access by unauthorized per-
              tems shall not be located in areas where the floor is  sonnel.
              located more than 75 feet (22 860 mm) above the low-
              est level of fire department vehicle access, or where the  1206.2.8.5.1 Cabinets.  Where stationary batteries
              floor level is more than 30 feet (9144 mm) below the   are contained in cabinets in occupied work centers,
              finished floor of the lowest level of exit discharge.  the cabinet enclosures shall be located within 10 feet
                                                                     (3048 mm) of the equipment that they support.
                Exceptions:
                                                                   1206.2.8.6 Signage. Approved signs shall be provided
                   1. Lead acid and nickel cadmium stationary stor-  on doors or in locations near entrances to stationary
                     age battery systems.                          storage battery system rooms and shall include the fol-
                   2. Installations  on noncombustible rooftops of  lowing or equivalent:
                     buildings exceeding 75 feet (22 860 mm) in      1. The room contains energized battery systems.
                     height that do not obstruct fire department
                     rooftop operations, where approved by the fire  2. The room contains energized electrical circuits.
                     code official.                                  3. The additional markings required  in  Section
              1206.2.8.2 Separation. Rooms containing stationary        1206.2.12 for the types of storage batteries con-
              storage battery systems shall be separated from other     tained within the room.
              areas of the building in accordance with Section 509.1  Exception: Existing stationary storage battery sys-
              of the  International Building Code. Battery  systems  tems shall be permitted to include the signage
              shall be allowed to be in the same room with the equip-  required at the time it was installed.
              ment they support.
                                                                     1206.2.8.6.1 Electrical disconnects. Where the sta-
              1206.2.8.3 Stationary battery arrays. Storage batter-  tionary storage battery system disconnecting means
              ies, prepackaged stationary storage battery systems and  is not within sight of the main service disconnecting
              preengineered stationary storage battery systems shall  means, placards or directories shall  be  installed at
              be segregated into stationary battery arrays not exceed-  the location of the main service disconnecting
              ing  50  kWh (180 megajoules) each. Each stationary    means indicating the location of stationary storage
              battery array shall be spaced not less than 3 feet (914  battery system disconnecting  means  in accordance
              mm)  from other stationary battery arrays and  from    with NFPA 70.
              walls in the storage room or area. The storage arrange-
              ments shall comply with Chapter 10.                    1206.2.8.6.2 Cabinet signage. Battery storage cabi-
                                                                     nets  provided in occupied  work centers in accor-
                Exceptions:                                          dance  with Section 1206.2.8.5  shall have exterior
                   1. Lead acid and nickel cadmium storage battery   labels that identify  the manufacturer  and model
                     arrays.                                         number of the system and electrical rating (voltage
                                                                     and current) of the contained battery system. There
                   2. Listed preengineered stationary storage bat-   shall be signs within the cabinet that indicate the rel-
                     tery systems and prepackaged stationary stor-   evant electrical and chemical hazards, as required by
                     age battery systems shall not exceed 250 kWh    Section 1206.2.12.
                     (900 megajoules) each.
                                                                   1206.2.8.7 Outdoor  installations. Stationary  storage
                   3. The fire code official is authorized to approve
                                                                   battery systems  located  outdoors shall comply with
                     listed, preengineered and prepackaged battery
                     arrays with larger capacities or smaller battery  Sections 1206.2.8.7 through 1206.2.8.7.4, in addition to
                     array spacing if large-scale fire and fault con-  all applicable requirements of Section 1206.2. Installa-
                                                                   tions in outdoor  enclosures or containers  that  can  be
                     dition  testing conducted or witnessed and
                     reported by an approved testing laboratory is  occupied for servicing, testing, maintenance and other
                     provided  showing that  a fire involving one  functions shall be treated as battery storage rooms.
                     array will not propagate to an adjacent array,  Exception: Stationary battery arrays in noncombus-
                     and be contained within the room for a dura-    tible containers shall not be required to be spaced 3
                     tion equal to the fire-resistance rating of the  feet (914 mm) from the container walls.

         224                                                                        2018 INTERNATIONAL FIRE CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   252   253   254   255   256   257   258   259   260   261   262