Page 368 - 2018_IFC
P. 368

CHAPTER 36

                                                         MARINAS





             User note:
                About this chapter: Chapter 36 addresses the fire protection and prevention requirements for marinas. It was developed in response to the
                complications encountered by a number of fire departments responsible for the protection of marinas as well as fire loss history in marinas
                that lacked fire protection. Compliance with this chapter intends to establish safe practices in marina areas, provide an identification method
                for mooring spaces in the marina, and provide fire fighters with safe operational areas and fire protection methods to extend hose lines in a
                safe manner.



                               SECTION 3601                          2. Materials  that meet a  peak rate of heat release not
                                  SCOPE                                exceeding 300 kW/m  where tested in accordance with
                                                                                        2
                                                                                                                 2
             3601.1 Scope. Marina facilities shall be in accordance with  ASTM E1354 at an incident heat flux of 50 kW/m  in
             this chapter.                                             the horizontal orientation.
                                                                  3603.5 Electrical equipment. Electrical equipment shall be
             3601.2 Plans and approvals. Plans for marina fire protec-
             tion facilities shall be  approved prior to installation. The  installed and used in accordance with its listing, Section 605
             work shall be subject to final inspection and approval after  of this code and Chapter 5 of NFPA 303 as required for wet,
             installation.                                        damp and hazardous locations.
                                                                  3603.6 Berthing and storage. Berthing and storage shall be
                                                                  in accordance with Chapter 7 of NFPA 303.
                               SECTION 3602
                               DEFINITIONS                        3603.7 Slip identification. Slips and mooring spaces shall be
                                                                  individually identified by an approved numeric or alphabetic
             3602.1 Definitions. The following terms are defined in Chap-  designator.  Space  designators shall be posted at the  space.
             ter 2:                                               Signs indicating the space designators located on finger piers
             FLOAT.                                               and floats shall be posted at the base of all piers, finger piers,
                                                                  floats and finger floats.
             MARINA.
             PIER.
                                                                                    SECTION 3604
             VESSEL.
                                                                           FIRE PROTECTION EQUIPMENT
             WHARF.
                                                                  3604.1 General. Piers, marinas and wharves with facilities
                                                                  for mooring  or servicing five or more  vessels, and marine
                               SECTION 3603                       motor fuel-dispensing facilities shall be equipped  with fire
                         GENERAL PRECAUTIONS                      protection equipment in  accordance  with Sections 3604.2
                                                                  through 3604.6.
             3603.1 Combustible debris. Combustible debris and rubbish
             shall not be deposited or accumulated on land beneath marina  3604.2 Standpipes. Marinas and boatyards shall be equipped
             structures, piers or wharves.                        throughout with standpipe systems in accordance with NFPA
                                                                  303. Systems shall be provided with hose connections located
             3603.2 Sources of  ignition.  Open-flame devices used for  such that no point on the marina pier or float system exceeds
             lighting or decoration on the exterior of a vessel, float, pier or  150 feet (15 240 mm) from a standpipe hose connection.
             wharf shall be approved.
                                                                     3604.2.1 Identification of standpipe outlets. Standpipe
             3603.3 Flammable or  combustible  liquid spills.  Spills of  hose connection locations shall be clearly identified by a
             flammable or combustible liquids at or on the water shall be  flag or other approved means designed to be readily visi-
             reported immediately to the fire department or jurisdictional  ble from the pier accessing the float system.
             authorities.
                                                                  3604.3 Access and water supply. Piers and wharves shall be
             3603.4 Rubbish containers. Containers with tight-fitting or  provided with fire apparatus access roads and water-supply
             self-closing lids shall be provided for temporary storage of  systems with on-site fire hydrants where required by the fire
             combustible debris, rubbish and waste material. The rubbish  code official. Such roads and water systems shall be provided
             containers shall be constructed entirely of materials that com-  and maintained in accordance with Sections 503 and 507.
             ply with any one of the following:
                                                                  3604.4 Portable fire extinguishers. One portable fire extin-
               1. Noncombustible materials.                       guisher of the ordinary (moderate) hazard type shall be pro-



             2018 INTERNATIONAL FIRE CODE ®                                                                      335
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   363   364   365   366   367   368   369   370   371   372   373