GENERAL REQUIREMENTS


                           SECTION 314                                  in accordance with Section 903.3.1.1, 903.3.1.2
                        INDOOR DISPLAYS                                 or 903.3.1.3
         314.1 General. Indoor displays constructed within any occu-  315.3.2 Means of egress. Combustible materials shall not
         pancy shall comply with Sections 314.2 through 314.4.   be stored in exits or enclosures for stairways and ramps.
         314.2 Fixtures and displays. Fixtures and displays of goods  315.3.3 Equipment  rooms. Combustible  material shall
         for sale to the public shall be arranged so as to maintain free,  not be stored in boiler rooms, mechanical rooms, electrical
         immediate and unobstructed  access  to  exits as required by  equipment rooms or in fire command centers as specified
         Chapter 10.                                             in Section 508.1.5.
         314.3 Highly combustible goods. The display of  highly  315.3.4 Attic, under-floor and concealed spaces. Attic,
         combustible goods, including but not  limited to fireworks,  under-floor and concealed spaces used for storage of com-
         flammable or combustible liquids, liquefied flammable gases,  bustible materials shall be protected on the storage side as
         oxidizing materials,  pyroxylin plastics and agricultural  required for 1-hour  fire-resistance-rated construction.
         goods, in main exit access aisles, corridors, covered and open  Openings  shall be protected by assemblies that are self-
         malls, or within 5 feet (1524 mm) of entrances to exits and  closing  and  are of noncombustible construction or solid
                                                                                     3
         exterior exit doors is prohibited where a fire involving such  wood core not less than 1 /  inches (44.5 mm) in thickness.
                                                                                      4
         goods would rapidly prevent or obstruct egress.         Storage shall not be placed on exposed joists.
         314.4 Vehicles. Liquid-fueled or gaseous-fueled vehicles,  Exceptions:
         boats or other motorcraft shall not be located indoors except
                                                                     1. Areas protected by approved automatic sprinkler
         as follows:                                                    systems.
           1. Batteries are disconnected except where the fire code  2. Group R-3 and Group U occupancies.
              official requires that the batteries remain connected to
              maintain safety features.                       315.4 Outside storage. Outside storage of combustible materi-
                                                              als shall not be located within 10 feet (3048 mm) of a lot line.
           2. Fuel in fuel tanks does not exceed one-quarter tank or 5
              gallons (19 L) (whichever is least).               Exceptions:
                                                                   1. The separation distance is allowed to be reduced to 3
           3. Fuel  tanks  and fill openings are closed and sealed  to
              prevent tampering.                                     feet (914 mm) for storage not exceeding 6 feet (1829
                                                                     mm) in height.
           4. Vehicles, boats or other motorcraft equipment are not
                                                                   2. The separation distance  is allowed  to be reduced
              fueled or defueled within the building.
                                                                     where the fire code official determines that hazard to
                                                                     the adjoining property does not exist.
                           SECTION 315                           315.4.1 Storage  beneath overhead projections  from
                       GENERAL STORAGE                           buildings. Where buildings are protected by an automatic
                                                                 sprinkler system, the outdoor storage, display and handling
         315.1 General. Storage shall be in accordance with Sections
         315.2 through 315.6. Outdoor pallet storage shall be in accor-  of combustible materials under eaves, canopies or other
         dance with Sections 315.2 and 315.7.                    projections or overhangs are prohibited except where auto-
                                                                 matic sprinklers are installed under such eaves, canopies
           Exception: Wood and wood composite pallets stored out-  or other projections or overhangs.
           doors at pallet manufacturing and recycling facilities and
           complying with Section 2810.                          315.4.2 Height. Storage in the open shall not exceed 20
                                                                 feet (6096 mm) in height.
         315.2 Permit required. A permit for miscellaneous combus-
         tible storage shall be required as set forth in Section 105.6.  315.5 Storage underneath high-voltage transmission lines.
                                                              Storage located underneath high-voltage transmission lines
         315.3 Storage in buildings. Storage of materials in buildings  shall be in accordance with Section 316.6.2.
         shall be orderly and stacks shall be stable. Storage of combus-
         tible  materials shall be  separated from  heaters or heating  315.6 Storage in plenums. Storage is prohibited in plenums.
         devices by distance or shielding so that ignition cannot occur.  Abandoned material in plenums shall be deemed to be stor-
                                                              age and shall be removed. Where located in plenums, the por-
           315.3.1 Ceiling clearance. Storage shall be maintained 2  tion of abandoned cables that are able to be accessed without
           feet (610 mm) or more below the ceiling in nonsprinklered  causing damage, or requiring demolition to the building shall
           areas of buildings or  not less than 18 inches  (457 mm)  be identified for future use with a tag or shall be deemed stor-
           below  sprinkler head deflectors in  sprinklered areas  of  age and shall be removed.
           buildings.
                                                              315.7 Outdoor pallet storage. Pallets stored outdoors shall
              Exceptions:                                     comply with Sections 315.7 through 315.7.7. Pallets stored
                1. The 2-foot (610 mm) ceiling clearance is not  within a building shall be protected in accordance with Chap-
                   required for  storage  along walls in nonsprin-  ter 32.
                   klered areas of buildings.
                                                                 315.7.1 Storage  beneath overhead projections  from
                2. The 18-inch (457 mm) ceiling clearance is not  buildings. Where buildings are equipped throughout with
                   required for storage along walls in areas of build-  an automatic sprinkler system, the outdoor storage of pal-
                   ings equipped with an automatic sprinkler system  lets under eaves,  canopies  or other projections  or over-

         58                                                                         2018 INTERNATIONAL FIRE CODE ®