Page 365 - 2018_Complete_14_Collection (1)_Neat
P. 365
EXTERIOR WALLS
1406.11.3.1 Prohibited occupancies. MCM shall not automatic sprinkler system in accordance with Section
be permitted on buildings classified as Group A-1, A-2, 903.3.1.1, the maximum percentage area of exterior
H, I-2 or I-3 occupancies. wall of any story covered with MCM panels and the
1406.11.3.2 Nonfire-resistance-rated exterior walls. maximum square footage of a single area of MCM
MCM shall not be permitted on exterior walls required panels in Table 1406.11.3.4 shall be increased 100 per-
to have a fire-resistance rating by other provisions of cent. The area of MCM panels shall not exceed 50 per-
this code. cent of the exterior wall area of any story or the area
1406.11.3.3 Specifications. MCM shall be required to permitted by Section 705.8 for unprotected openings,
comply with all of the following: whichever is smaller.
1. MCM shall have a self-ignition temperature of 1406.11.4 Installations up to 75 feet in height (Option
650°F (343°C) or greater when tested in accor- 2). MCM shall not be installed more than 75 feet (22 860
dance with ASTM D1929. mm) in height above grade plane where installed in accor-
2. MCM shall conform to one of the following com- dance with Sections 1406.11.4.1 through 1406.11.4.4.
bustibility classifications when tested in accor- Exception: Buildings equipped throughout with an
dance with ASTM D635: automatic sprinkler system in accordance with Section
Class CC1: Materials that have a burning extent 903.3.1.1 shall be exempt from the height limitation.
of 1 inch (25 mm) or less when tested at a 1406.11.4.1 Minimum fire separation distance.
nominal thickness of 0.060 inch (1.5 mm) or MCM shall not be installed on any wall with a fire sep-
in the thickness intended for use. aration distance less than 30 feet (9 144 mm).
Class CC2: Materials that have a burning rate of Exception: Where the building is equipped through-
1
2 / inches per minute (1.06 mm/s) or less out with an automatic sprinkler system in accor-
2
when tested at a nominal thickness of 0.060 dance with Section 903.3.1.1, the fire separation
inch (1.5 mm) or in the thickness intended for distance shall be permitted to be reduced to not less
use. than 20 feet (6096 mm).
1406.11.3.4 Area limitation and separation. The 1406.11.4.2 Specifications. MCM shall be required to
maximum area of a single MCM panel and the mini- comply with all of the following:
mum vertical and horizontal separation requirements 1. MCM shall have a self-ignition temperature of
for MCM panels shall be as provided for in Table 650°F (343°C) or greater when tested in accor-
1406.11.3.4. The maximum percentage of exterior wall dance with ASTM D1929.
area of any story covered with MCM panels shall not 2. MCM shall conform to one of the following com-
exceed that indicated in Table 1406.11.3.4 or the per- bustibility classifications when tested in accor-
centage of unprotected openings permitted by Section dance with ASTM D635:
705.8, whichever is smaller. Class CC1: Materials that have a burning extent
Exception: In buildings provided with flame barri- of 1 inch (25 mm) or less when tested at a
ers complying with Section 705.8.5 and extending nominal thickness of 0.060 inch (1.5 mm), or
30 inches (760 mm) beyond the exterior wall in the in the thickness intended for use.
plane of the floor, a vertical separation shall not be Class CC2: Materials that have a burning rate of
required at the floor other than that provided by the 2 / inches per minute (1.06 mm/s) or less
1
2
vertical thickness of the flame barrier. when tested at a nominal thickness of 0.060
1406.11.3.5 Automatic sprinkler system increases. inch (1.5 mm), or in the thickness intended for
Where the building is equipped throughout with an use.
TABLE 1406.11.3.4
AREA LIMITATION AND SEPARATION REQUIREMENTS FOR MCM PANELS
MINIMUM SEPARATION
MAXIMUM PERCENTAGE OF MCM PANELS
FIRE SEPARATION COMBUSTIBILITY AREA OF EXTERIOR WALL MAXIMUM SINGLE AREA
DISTANCE CLASS OF MCM COVERED WITH MCM OF MCM PANELS (feet)
(feet) (square feet)
PANELS
Vertical Horizontal
Less than 6 — Not Permitted Not Permitted — —
CC1 10 50 8 4
6 or more but less than 11
CC2 Not Permitted Not Permitted — —
11 or more but less than or CC1 25 90 6 4
equal to 30 CC2 15 70 8 4
CC1 50 Not Limited 3 a 0
More than 30
CC2 50 100 6 a 3
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m . 2
a. For reductions in the minimum vertical separation, see Section 1406.11.3.4.
338 2018 INTERNATIONAL BUILDING CODE ®