Internal/External Water Circuits
TA 1100 – 0110 TA 1000 – 0206/TA 1000 – 0200
Temperature fluctuations Value Unit Range
→ Return water temperature -20/+3°C (TA 1100 Appearance - Clear, free of
- 0110) sediments
→ limits for oil-, jacket water- temperature Ph value at 25°C - 6.5 – 7.5
→ Return water temperature fluctuation <
10°C/min. Total Hardness °dH ppm < 15
(CaCO3)
< 250
→ Return water temperature control valve
Example internal jacket water circuit
(excerpt)
Water quality
→ TA 1000 – 0206 or TA 1000 – 0200
All rights reserved May 19