Internal/External Water Circuits



                            TA 1100 – 0110 TA 1000 – 0206/TA 1000 – 0200




                         Temperature fluctuations                                                                Value                     Unit             Range


                             → Return water temperature -20/+3°C (TA 1100                                        Appearance                -                Clear,  free of
                             - 0110)                                                                                                                        sediments
                             → limits for oil-, jacket water- temperature                                        Ph value at 25°C          -                6.5 – 7.5

                             → Return water temperature fluctuation <
                             10°C/min.                                                                           Total Hardness            °dH ppm          < 15
                                                                                                                 (CaCO3)
                                                                                                                                                            < 250
                             → Return water temperature control valve
                                                                                                               Example internal jacket water circuit

                                                                                                               (excerpt)













                         Water quality


                             → TA 1000 – 0206 or TA 1000 – 0200




                                    All rights reserved      May 19