Page 172 - Engine IQflip'21
P. 172

Foundation requirements










                            Technical instruction no: 1000-0041 (Requirements for arrangement surface of INNIO

                            Jenbacher installations)



                            Installation surface:


                            capable to withstand static and dynamic load of INNIO Jenbacher plants



                            Static load = Plant weight (filled condition)
                            Dynamic load = ≤ 3% of plant weight



                            size of the installation surface is:
                            frame length + 200 mm [7,874 in]) x (frame width + 200 mm [7,874in]



                            flatness requirement for the installation surface of the installation
                            is ±1.5 mm/m with a maximum of is ± 5 mm

                            measured across the entire arrangement surface








                                    All rights reserved      May 19