Page 187 - Engine IQflip'21
P. 187

Medium voltage generators > 1000V



                            General cabling





                             Technical instruction no: 1100-0114 (Installation of electrical equipment for INNIO Jenbacher
                             generator sets)

                             Medium- voltage cable:
                             Flexible, finely stranded, copper single conductors must be used!
                             Conductor stranding: in accordance with IEC 60228/CENELEC HD 383/VDE 0295 Class 5

                             Recommended:

                             ⁄ FELTOFLEX Typ. NTMCWOEU (Single-core conductor)

                             ⁄ PROTOLON Typ. NTMCGCWÖU (Single-core conductor)

                             Stress cone ends at generator connection:
                             The available space between the terminal clamps (isolator) and the strain relief brackets is approx.
                             300 mm. Consequently, only "short" stress cones can be used…

                             Cable lugs:

                             These should be dimensioned in such a way that they are suitable
                             for the powers (vibrations) occurring in the generator.

                             Screwed cable glands:
                             nickel-plated brass (no threaded plastic connections) or the built-in rubber glands