Electrical Miscellaneous




                   Power panel configuration and requirements


                            Minimum requirements:

                            ⁄ Circuit breaker 3 pole (draw out type for MV) with motor drive (24VDC), suitable for

                               synchronizing and BLACK OUT Start with de excited alternator (No alternator voltage is available)
                            ⁄ 24 (110) VDC closing coil, closing time max. 70 msec. from INNIO Jenbacher interface until

                               contacts of the generator C.B. are closed, transmission time for the STATUS feedback signal max.
                               30msec.

                            ⁄ 24 (110) VDC shunt trip coil;  trip time  max. 60 msec. from INNIO Jenbacher interface until

                               contacts of the generator C.B. are opened, transmission time for the STATUS feedback signal
                               max. 30msec.

                            ⁄ 24 (110) VDC under voltage trip coil

                                • On | Off command from INNIO Jenbacher synchronizing only: Continuous contacts (1 NO and 1 NC) with 24
                                  VDC, 10 A (110VDC, 0,5A) load rating.

                                • Over current and short circuit protection with primary or secondary relays.

                                • Current Transformer and Voltage transformer (Project specific)

                                • Generator transient over voltage surge protection according TA-Nr. 1100-0112

                            Further info – “technical specification of control”
                            section 4.5.1 requirements for customer swichgear