Electrical Miscellaneous
Power panel configuration and requirements
Minimum requirements:
⁄ Circuit breaker 3 pole (draw out type for MV) with motor drive (24VDC), suitable for
synchronizing and BLACK OUT Start with de excited alternator (No alternator voltage is available)
⁄ 24 (110) VDC closing coil, closing time max. 70 msec. from INNIO Jenbacher interface until
contacts of the generator C.B. are closed, transmission time for the STATUS feedback signal max.
30msec.
⁄ 24 (110) VDC shunt trip coil; trip time max. 60 msec. from INNIO Jenbacher interface until
contacts of the generator C.B. are opened, transmission time for the STATUS feedback signal
max. 30msec.
⁄ 24 (110) VDC under voltage trip coil
• On | Off command from INNIO Jenbacher synchronizing only: Continuous contacts (1 NO and 1 NC) with 24
VDC, 10 A (110VDC, 0,5A) load rating.
• Over current and short circuit protection with primary or secondary relays.
• Current Transformer and Voltage transformer (Project specific)
• Generator transient over voltage surge protection according TA-Nr. 1100-0112
Further info – “technical specification of control”
section 4.5.1 requirements for customer swichgear