Steam Boiler/Heat Recovery Steam Generation












                            Rules of Thumb                                                                                        Engine
                                                                                                                           Exhaust Temp
                            ⁄ Q from exhaust = Q to Steam
                               (Less blow-down & radiant loss)

                            ⁄ Typical Steam pressure are up to 300 psig

                            ⁄ 1 ton of steam required energy 680 Kwh                                                                                                          Stack Temp

                               (feed water temp 80C)

                            ⁄ Stack temp limited by fuel sulfur content

                            ⁄ Pinch point – The pinch point is the minimum
                               temperature difference between the flue gas
                               and

                               the EVAP saturation temperature. The surface
                               grows exponentially with lower pinch point temp.

                               Steam Tools use 20C. (Aggressive 14C)