Page 57 - ISCIR2007
P. 57

0.30 mm wide were observed in RC beams (B4, B4a, B5,
         B5a  and  B6  in  Figure  2)  under  normal  operating
         service.  This  was  attributed  to  the  lack  of  sufficient
         transversal  reinforcement  and  the  low  concrete
         strength as evidenced by the as-built document review.
         It  was  proposed  to  repair  the  cracked  RC  elements
         using  epoxy  injections  prior  to  carrying  out  any
         strengthening  work.  Several  strengthening  schemes
         were proposed including traditional solutions, such as
         externally bonded steel plate (EBS), concrete sectional
         enlargement  and  externally  bonded  fibre  reinforced
         polymer  (EBR)  for  defected  RC  beams  to  resist  the
         actual, increased design live load. An externally bonded
         system  using  manual  lay-up  CFRP  laminates  was
         chosen as a repair / strengthening solution to increase   Figure 2 Location of defects found in RC beams at the
         the  shear  capacity  of  the  deficient  RC  elements.  The   2nd floor
         strengthening design and construction procedure were
         in  accordance  to  ACI  440.2R  [3]  and  fib  14  [4].  The
         strengthening work was done and completed in 2014.
         Currently,  the  building  and  the  plant  are  still  in
         operation with a periodic inspection carried out every
         year.
         Structural Damage Assessment
                                                                                    Photo B4a
                                                            Photo B4
         Structural damage assessment of the RC building   (crack width = 0.30 mm)   (crack width = 0.30 mm)
         The condition survey of structural components for the
         RC  building  was  implemented  to  examine  and  assess
         the  current  level  of  damage  and  deterioration  of  the
         structure, and determine the preliminary serviceability
         condition of the structural components of the building.
         The  rating  point  system  was  used  to  evaluate
         serviceability, and to compare the current and newly-  Photo B5            Photo B5a
         built structural condition only, without determining the   (crack width = 0.30 mm)   (crack width = 0.35 mm)
         load capacity of the structural components (see Figures   Figure 3 Location of shear cracks found in RC beams at
         2 and 3). For damage due to current loading, repair or        the 2nd floor
         replacement, terms were added  to the criteria for the   Design verification according to ACI 318
         structure  in  its  current  condition,  i.e.  a  structural
         element  that  shows  small  defects,  good  maintenance   During  the  construction  of  the  building,  it  was  found
         and  good  construction  practice  was  given  a  condition   that the concrete strength (18 MPa) was lower than the
         rating of 2 or “Fair condition”. If the same element had   design value (30 MPa) therefore the in-situ strength of
         some effects/damages from current loading to the level   concrete was used to re-assess the actual load capacity.
         the replacement of the element will be of more benefit   A  yield  strength  of  392MPa  was  used  for  the  steel
         to  the  whole  structure  than  rehabilitation,  then  the   reinforcement  as  per  inspection.  The  original  design
         term  “Replacement”  was  recommended  for  “Fair   floor  live  loads  ranged  from  5  to  10  kN/m2  and  the
         condition” (adopted from RILEM Technical Committee   new live load on the 2nd floor is planned to increase by
         104 [5]).                                      up  to  125%  of  the  original  design.  The  design  check
                                                        considers  the  factored  load  i.e  (Mu)  and  nominal
                                                        strength of the section (Mn) multiplied by the strength
                                                        reduction factor (Φ) according to ACI 318 [6]. Figure 4
                                                        shows a 3D FE model of the Pelletizer building.



                           “Innovative Seismic Strengthening System for Concrete Structures”
                                        © 2017 | T Imjai & R. Garcia (Eds.)
                                                  -- 55 --
   52   53   54   55   56   57   58   59   60   61   62