This report is not valid if the serial number has been defaced or altered
IPN3/0385688
SCHEDULE OF CIRCUIT DETAILS
FOR THE PRIMARY DISTRIBUTION BOARD
CIRCUIT DETAILS
TO BE COMPLETED IN EVERY CASE
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Location of distribution board:
Distribution
board designation:
DB1
Basement
Supply to distribution Main intake board is from:
Overcurrent protective device for the distribution circuit:
Type: 1362 BS(EN)
No of phases:
Associated RCD (if any): BS(EN)
Nominal V voltage:
IÜ mA
1
230
Rating:
100
A
RCD No of poles:
Circuit designation
Circuit conductors: csa
(s)
Overcurrent protective devices
RCD
(É)
Live
(mmâ)
cpc
(mmâ)
BS (EN)
(A)
(kA)
(mA)
1
Water heater
B
A
1
2.5
1.5
0.4
60898 MCB
B
20
6
2.30
2
Lights - upper fire escape
B
A
5
1.5
1.5
0.4
60898 MCB
B
10
6
4.60
3
Lights - ground floor/stairs
B
A
17
1.5
1.5
0.4
60898 MCB
B
10
6
4.60
4
Unknown
B
A
2.5
1.5
0.4
60898 MCB
B
10
6
4.60
5
Lights - basement/lower fire escape
B
A
8
1.5
1.5
0.4
60898 MCB
B
16
6
2.88
6
Entryphone
O
A
1
2.5
1.5
0.4
60898 MCB
B
10
6
4.60
7
Sockets - basement
O
A
4
2.5
1.5
0.4
61009 RCD/RCBO
B
32
6
30
1.44
8
9
10
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
Þ See Table 4A2 of Appendix 4 of BS 7671
This form is based on the model shown in Appendix 6 of BS7671
Published by the NICEIC a part of the Ascertiva Group © Copyright The Electrical Safety Council (July 2011)
Page 7 of 8
A
B
C
D
CODES FOR TYPE OF WIRING
EFG
H
O (Other - please state)
Thermoplastic insulated/ sheathed cables
Thermoplastic cables in metallic conduit
Thermoplastic cables in non metallic conduit
Thermoplastic cables in metallic trunking
Thermoplastic cables in non metallic trunking
Thermoplastic/ SWA cables
Thermosetting/ cables
Mineral- insulated cables
See next page for Schedule of Test Results
Circuit number and phase
Type of wiring (see code)
Reference method
Number of points served
Max. disconnection time permitted
by BS 7671
Type No
Rating
Short-circuit capacity
Operating current, IÜ
Maximum Ö permitted by BS 7671
Original (To the person ordering the work)


































































































   905   906   907   908   909