Page 6 - GI ZA12 Expansion Def 2017 17_3.xlsx
P. 6
Combination Deflection/Expansion Fittings
For Rigid Metal Conduit & IMC
Type AFDF
Provide Deflection and straight line movement beyond 3/4"
Use:
The assembly shown can be used where
allowance for expansion and deflection
must be provided but the 3/4” straight line
movement in either direction which our Type
DF expansion/deflection fitting permits is
not sufficient. By combining the Type DF
fitting with our Type AF expansion fitting, a
straight line movement of 2” in either
direction (total movement of 4”) is provided.
Features:
• Fitting assembly can be used embedded
in concrete as shown, or can be used in
exposed locations.
• Fittings include standard Type DF and AF fittings, Approx.
Trade Max Dia
bonding jumper, insulating bushing, and short nipple. Catalog # Overall
Size (IN) (IN)
Length
Material: 1/2 AFDF-50 2 1/4 15
Material: 3/4 AFDF-75 2 1/2 15 1/8
Sleeve - Silicone 1 AFDF-100 2 3/4 15 5/8
NFPA Profile: 1 1/4 AFDF-125 3 1/8 15 7/8
Flammability - Zero 1 1/2 AFDF-150 3 1/2 15 7/8
Reactivity - Zero 2 AFDF-200 4 17 1/4
UV resistance - High 2 1/2 AFDF-250 4 1/2 18
End Couplings -ZA12 3 AFDF-300 5 1/8 18 5/8
Bonding Jumper - Tinned Copper Braids 3 1/2 AFDF-350 6 19 3/4
Bands - Stainless Steel 4 AFDF-400 6 5/8 20
All other metal parts are malleable, ductile iron or steel 5 AFDF-500 8 21
UL Listed: E31413
Wet or dry locations - use with How to Order Example
Type BJ external bonding jumpers, Finish
per NEC 250.98 Standard ZA12 AFDF-50
Optional Sizes: Aluminum AFDF-50 AL
Other sizes available. Fittings can be furnished to provide additional Polyolefin Coated AFDF-50 GG
linear conduit movement beyond 4”. Specify Electric Galvanized AFDF-50 EG
"AF8DF" for 8" linear movement, 4” in either direction. Contact
your local representative for pricing and availability.
Gafco Industrial, LLC. 7128 Reynolds Dr. Sedalia, CO 80135
P (303) 339-3280 | F (303) 339-3279