Page 25 - CHIRP Annual Digest 2017
P. 25

CHIRP Annual Digest 2017



            Article. 17                                       vals. It should be noted that in a shore-side environment
                                                              such as crane operations, a five year change out would be
            Battery fire                                      considered unacceptable.

            In the early hours of the morning during a period of adverse   In addition, Regulation 20 of SOLAS III no longer requires
            weather the fire alarm in the vessel’s battery locker was   wires to be end-for-ended. In an amendment, the end-for-
            activated. The crew mustered and a fire team assembled.   ending has been replaced by an inspection regime to identify
            Upon investigation it was discovered that there was a small   deterioration. This means however that the same sector of
            flame and sparks being emitted from a spare battery that   wire rope could be positioned over the davit and fall block
            was stored in the battery locker on the top shelf.   sheaves for the entire five years of service of the wire rope.
                                                              In the light of recent reports of accidents involving wire rope
            The battery had been delivered during a previous port call   falls, this policy has to be questioned.
            and stored within the battery locker. Unfortunately, it had
            been placed on a storage shelf with no attempt to secure
            it in place.

            During a period of heavy weather, the battery tipped onto its
            side and slid against the steel lining of the bulkhead. As the
            battery terminals were not covered, this caused the battery
            to short and led to it overheating.
            Once the battery had reached ignition temperature the cas-
            ing melted, setting off the fire alarm.
            Corrective Action
               • All batteries, including spares, must be secured in place   Typical wire failure in way of the davit head / sheave –
              to prevent movement                                     Picture courtesy BBC News/J. McArthur
               • All spare batteries should have the terminals covered
              with insulating material to prevent accidental shorting   Any seafarer who has end-for-ended wire rope falls will be
                                                              aware that the ropes, when removed from the davits, are
                                                              usually deformed in way of the sharp turns of the sheaves
                                                              and do not return to straightened alignment. If a material
                                                              deforms and does not return to its original shape it has
                                                              passed its elastic limit and moved into plastic deforma-
                                                              tion. This is normally taken as the beginning of fatigue and
                                                              precedes the cracking of surfaces referred to in laboratory
                                                              reports on samples from failed wire ropes.

                                                              Wires often fail at a position around a sheave. They would
            Damaged battery after the fire.                   have been straightened only on those occasions when the
                                                              boat was lowered. Bending would cause the strands on the
                         The above article was published in MFB48  outside of the bend to open and expose the inner surfaces
                                                              to the elements. Unless effectively coated by grease, these
            Article. 18                                       surfaces would have relied on their galvanised coating alone
                                                              to protect them from the corrosive influences of the marine
            Advisory Board Insight:                           environment. The galvanised surfaces, if deficient in lubri-
            Lifeboat Falls                                    cant, would wear and potentially break down. Furthermore
                                                              the position, within the throat of the fall block, could be diffi-
                                                              cult to reach to apply grease effectively. Sensitivities regard-
            The maritime industry continues to report a high number of   ing pollution and cleanliness, combined with a desire to limit
            accidents involving lifeboats, particularly at drills and when   exposure of seafarers to dangers when working at height,
            launching boats. Failures have been attributed to both the   would serve to discourage regular greasing.
            poor design of hooks and the failure of wires. Many of these
            incidents have resulted in severe injuries or fatalities. It is
            fair to say then, that despite the amended regulations and
            guidance from IMO, including support from the Industry Life-
            boat Group, (ILG), a great deal of work needs to be done to
            prevent reoccurrence of the incidents.

            Wire Ropes
            Looking at wires first, the current SOLAS requirement is for
            wires used as falls to be changed out every five years. This
            is an arbitrary period intended to coincide with docking inter-



                                                           24
   20   21   22   23   24   25   26   27   28   29   30