Page 90 - Vessel Sanitation Program 2018 Operations Manual
P. 90

VSP 2018 Operations Manual



                              5.7.1.2.9     Location (08)
                                            BACKFLOW PREVENTION DEVICES and AIR GAPS must be
                                            ACCESSIBLE for inspection, testing, service, and maintenance. If
                                            access panels are required, provide panels large enough for testing,
                                            service, and maintenance.

                          5.7.1.3    Air Supply Connections


                              5.7.1.3.1     Air Supply (08)
                                            A compressed air system that supplies pressurized air to both
                                            nonpotable and POTABLE WATER pneumatic tanks must be
                                            connected through a press-on (manual) air valve or hose.

                              5.7.1.3.2     Separate Compressor
                                            A fixed connection may be used when the air supply is from a
                                            separate compressor used exclusively for POTABLE WATER
                                            pneumatic tanks.

                       5.7.2   Backflow Prevention Device Inspection and Testing

                          5.7.2.1    Maintenance


                              5.7.2.1.1     Maintained (08)
                                            BACKFLOW PREVENTION DEVICES must be maintained in
                                            good  repair.


                          5.7.2.2    Inspection and Service

                              5.7.2.2.1     Schedule (08)
                                            BACKFLOW PREVENTION DEVICES should be periodically
                                            inspected and any failed units must be replaced.

                                            A visual check must be completed for all nontestable
                                            BACKFLOW PREVENTION DEVICES and AIR GAPS at least
                                            annually.

                              5.7.2.2.2     Test Annually (08)
                                            BACKFLOW PREVENTION DEVICES requiring testing (e.g.,
                                            reduced pressure BACKFLOW PREVENTION DEVICES and
                                            PRESSURE VACUUM BREAKERS) must be inspected and
                                            tested with a test kit after installation and at least annually. Test
                                            results showing the pressure differences on both sides of the valves
                                            must be maintained for each device.