Page 2 - FQ09206-R9.EllisCorp-Shaw.for Nevada Linen
P. 2

Ellis Corporation                                                Proposal No. Q09206-R9
               1400 West Bryn Mawr Avenue
               Itasca, IL  60143                                                Date:  April 26, 2017

               Attention:  Mr. Jim Shaw                                         Salesman:    MFL/GT

               E-mail:  jshaw11@aol.com

               Subject:   NEVADA LINEN


               Jim, my recommendation is that Nevada Linen purchases the Hot Water Heater and Hot Water
               Tank with Pumps at this time and the remainder in the future with the remainder of the Ellis
               Wash  Floor.    As  per  our  visit  to  Nevada  Linen,  we  are  pleased  to  quote  for  following
               Equipment:

                   Two (2)  4,000 Gallon Tanks.
                            84” diameter x 13’ high, Type 304 Stainless Steel.
                           Note: Reuse Water Tank top   reinforced for a shaker screen.   One (1) Hot Water;
                                 One (1) Reuse.
                           PRICE:  $16,980.00 (EACH)

                 Three (3)  Pumps on a Prepiped Prewired Skid for Hot & Tempered Water.
                           Pumps are 400 GPM @ 110’ T.D.H., Pumps 3500 RPM.  TEFC Inverter Duty Motors.
                           All piping is Type 304L Stainless Steel. 15HP.
                           PRICE:  $21,650.00

                   One (1)  Shaker Screen for Reuse Water.
                           PRICE:  $15,395.00

                  Two (2)  Pumps on Prepiped/Prewired Skid for Reuse Water.
                           Pumps are 300 GPM at 110’ T.D.H.
                           PRICE:  $11,280.00

                  One (1)  Heat Reclaimer System, 4-6”- 30’ long with Four-way Valve, Throttle Valve, Floor
                           Stands and Controls.  5 Deg. F. approach with Waste Water Pumps. Note:  Two (2)
                           sections to be added to two (2) existing sections and relocated to the boiler room.
                           PRICE:  $60,985.00
                           Note:  Waste Water Velocity is 3.5 feet per second.

                  One (1)  PID Level Control Type Panel with Digital Temperature Displays.
                           Five (5) AC Inverters Main Panel Disconnect, Touch Screen for Pump and System
                           Status. Includes pit level controls
                           PRICE:  $23,600.00
   1   2   3   4   5   6   7