Page 2 - FQ10474-A.GVA Northwest.DCWH
P. 2

GVA Northwest                                                    Proposal No. Q10474-A
               4434 SE Division St.
               Portland, OR 97206                                               Date:  April 6, 2017

               Attention:  Mr. John Hilton                                      Salesman: DGB/kr

               E-mail:  jhilton@gvanw.com                                       Tel:   502-233-8811

               Subject:  NATIONAL FROZEN FOODS                                  Cell:  503-539-9971


               We are pleased to quote the following, Fully Packaged Model DC 3000S DIRECT CONTACT
               WATER HEATER with Integral 1,300 Gallon Tank, Delivery Pump and System Controls, to
               be installed by the purchaser.  This system is designed on the basis of the information supplied
               to us by your plant to handle the following approximate quantities and temperatures and
               produce the stated results.

               CUSTOMER REQUIREMENTS:

                            Hot Water ---------------------------------------- 4,200 GPH (70 GPM @ 130 Deg. F.)
                            Cold Water (Minimum) -----------------------------------------------------   50 Deg. F.
                            Cold Water (Average) -------------------------------------------------------   60 Deg. F.
                            Natural Gas Pressure (1,000 BTU/FT ) ------------------  1 PSIG @ 3,000 FT /HR.
                                                                3
                                                                                                  3

               HEATER CAPACITY:

               Direct Contact Water Heater (Patent No. 4574775) is rated at 3,000,000 BTU/HR and is capable
               of heating 70 GPM from 50 to 130 Deg. F. at sea level to 1,000 foot elevation.

               ESTIMATED ANNUAL VALUE OF HEAT LOAD REDUCTION:

               Based upon heating 4,200 GPH of water from 60 to 130 Deg. F., 12 hours per week for 52 weeks
               per year, and natural gas at a cost of $6.00 per 1,000 CU FT., the annual cost reduction would be
               $3,840.00 when compared to a conventional gas-fired heater or boiler system operating at 70%
               system efficiency.

               LUDELL EXTENDED WARRANTEE:

               Ludell warrants its water heaters against defects in material and workmanship, under normal
               use and service for a period of five (5) years after shipment for the fabricated stainless steel shell
               and one (1) year for all other components. Ludell's obligation is limited to repair or replacement
               f.o.b. Ludell's plant.  Please note that customer supplied water chemistry may adversely affect
               the equipment materials of construction.  If the water supply is aggressive, acidic or high in
               chlorides a higher-grade stainless steel alloy must be utilized.  Contact Ludell for a quote
               revision if your supply water chemistry is of poor quality.
   1   2   3   4   5   6   7