5.5 Choosing the Inverter
The combinations of motor power ratings and inverters listed in the table shows the use of motors in which the volt-
age rating is equal to that of the mains power. ADV200 - 4
For motors with different voltage ratings the inverter must be chosen according to the current rating of the motor.
The combinations listed in the table thus show the current that can be delivered by the drive during continuous op-
eration and overload conditions, according to the mains voltage.
The same engineering criteria apply for operations with additional derating factors:
• Kt Ambient temperature
• Kf Switching frequency ADV200-DC
• Kalt Altitude of installation
5.6 Input Data
Overvoltage Undervoltage ADV200 - 6
Input voltage threshold threshold Total harmonic
Sizes Input frequency distortion
ADV80 Uln (Overvoltage) (Undervoltage)
[Vac] [Hz] [Vdc] [Vdc] [THD] %
1004
1005 ADV100
1007
1015
380 Vcc
2022 (for 380, 400Vac ), > 100 %
2030 (without mains choke)
Three-phase mains
400 Vcc
2040 400 Vac -15% ... 480 Vac 50/60 Hz, ± 5% 800 (for 420, 440 Vac ), < 50 % ADV80
+10%
2055 (with optional mains
2075 415 Vcc choke)
(for 460, 480 Vac )
2110
3150
3185 AFE200
3220
AC input current for continuous operation
In (@ I2n) Max. short circuit
Sizes Connections with Connections without power without input
ADV80 three-phase input choke three-phase input choke choke (Zmin=1%) FFE200
@ 400 Vac [A] @ 480 Vac [A] @ 400 Vac [A] @ 480 Vac [A] [kVA]
1004 1.3 1.1 2.1 1,7 85
1005 1.6 1.3 2.6 2 115
1007 2.1 2 3.4 3.1 160 SMB200
1015 4 3.6 5.9 5.3 270
2022 5.6 5 8.1 7.2 380
2030 7.1 6.5 10.2 9.1 500
2040 9.6 8.8 13 12 650
2055 10.8 9.1 17 14.5 850
2075 16 14.3 19 17 1115 PROGRAM.
2110 23 21 28 26 1600
3150 33 31 40 38 2200
3185 38 36 47 44 2700
APPENDIX
3220 43 40 53 49 3200