Page 91 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 91

Gefran Spa - Drive & Motion Control Unit • www.gefran.com               91





          6.2	 General	Characteristics

           Power supply:      380Vac -15% …500Vac +5%,          Standard	supply	configuration
                               50/60Hz (versions -4 and -4A)                                                        ADV200 - 4
                                                               Integrated KB_ADV programming keypad
                               500Vac -10% …690Vac +10%,       Regulation:
                               50/60Hz ( -6 and -6A versions)
                                                                 • 2 bipolar analog inputs (Voltage/Current)
           Power ratings:     from 22kW to 1.65MW               • 2 bipolar analog outputs
           Cosphi ≥ 0.99                                          (1: Voltage/Current, 1: Voltage)
           THD ≤  3% (Considering a network with voltage THD of less than 2%).     • 6 digital inputs (PNP/NPN)    ADV200-DC
           Overload 150% for 60 sec every 5 minutes (Heavy duty) or      • 2 digital outputs (PNP/NPN)
            110% for 60 sec every 5 minutes (Light duty)         • 2 relay outputs, single contact
           Integration of up to 2 options onboard the drive     • RS485 serial line (Modbus RTU)
           GF-eXpress multi-language programming SW (5 languages)
           IP20-rated protection (IP00 size 7 and parallel)     Options
           Reference resolution:   Digital = 15-bit + sign         • LCL type line input filter, is composed by one Input choke   ADV200 - 6
                               Analog input = 11-bit + sign     and one LC filter (mandatory)
                               Analog output = 11-bit + sign
                                                                 • Pre-charge kit, includes fuses, resistors and pre-charge con-
                                                                tactor (mandatory)
            Fieldbus	management
                                                                 • External EMI mains filter

                                                      ®         Conformity
                                                                                                                    ADV100
                                                               Climatic conditions   EN 60721-3-3
                                                               Electrical safety   EN 50178, EN 61800-5-1,
                                                                                    UL508C, UL840 pollution level 2
                                    •
                                                               Vibrations          EN 60068-2-6, test Fc.
                                                               EMC                 EN61800-3                       ADV80
                                                                Environmental	conditions
                                                               Ambient temperature:   -10°C ... +40°C (+14°F ...+104°F),
                                                                                    +40°C…+50°C (+104°F…+122°F)
                                                                                    with derating
                                                                                                                    AFE200
                                                               Altitude:           Max 2000 m.
                                                                Markings
                                                                                    Complies with the EEC directive
                                                                                    concerning low voltage equipment
                                                                                    Complies with directives for the
                                                                                    American and Canadian market.
                                                                                    (Sizes AFE200-...-6/6A with 690 V power   FFE200
                                                                                    supply are not UL-marked.



                                                                                                                    SMB200





                                       AFE200
                                                               ADV200 DC      ADV200 DC       ADV200 DC             PROGRAM.










                                                                                                                    APPENDIX
             Controlled power exchange on DC-bus
            circuit: excess energy re-introduced into
                             the mains
   86   87   88   89   90   91   92   93   94   95   96