857-400
3 JUMPFLEX Signal Conditioners
®
172 Isolation Amplifier, with Zero/Span Adjustment
Configuration via:
DIP switch
<_________ 96 mm/3.76 in _________> GND 1 1 2 IN OUT 5 OUT+
IN+
6 GND 2
Us+
8 GND 3
_> GND 3 3 4 POWER 7 Us+
____________
_>
6 mm/0.23 in
<_________ 94 mm/3.68 in _________>
Short description: Pack.
The configurable 857-400 Isolation Amplifier is used to convert, amplify, filter Description Item No. Unit
and electrically isolate analog standard signals. ®
JUMPFLEX Signal Conditioner, for DIN 35 rail 857-400 1
Isolation Amplifier, with Zero/Span Adjustment
Characteristics:
• Zero/span adjustment across the entire measuring range
• Calibrated scale switching
• Switchable max. operating frequency
• Safe 3-way isolation with 2.5kV test voltage to EN 61140
Technical Data Technical Data
Configuration: Environmental requirements:
Configuration DIP switch Ambient operating temperature -25 °C ... +70 °C
Input: Storage temperature -40 °C ... +85 °C
Input signal 0 ... 20 mA, 4 ... 20 mA, Safety and protection:
0... 5 V, 0 ... 10 V, 2 ... 10 V, 1 ... 5 V Test voltage (input/output/supply) 2.5 kV AC, 50 Hz, 1 min
(calibrated switchable) Connection and type of mounting:
®
Input resistance ≤ 50 Ω (In = mA) Wire connection CAGE CLAMP S
≥ 100 kΩ (In = V) Cross sections solid:
Output: 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Output signal 0 ... 20 mA, 4 ... 20 mA, fine-stranded:
0... 5 V, 0 ... 10 V, 2 ... 10 V, 1 ... 5 V 0.34 mm² ... 2.5 mm² / AWG 22 ... 14
(calibrated switchable) Strip lengths 9 ... 10 mm / 0.37 in
Load impedance 600 Ω (Out = mA) Dimensions and weight:
2 kΩ (Out = V) Dimensions (mm) W x H x L 6 x 96 x 94
General specifications: Height from upper-edge of DIN 35 rail
24V DC Weight 36.8 g
Nominal supply voltage V S
Supply voltage range 16.8 V ... 31.2 V Standards and approvals:
Current consumption at 24 V DC ≤ 25 mA Conformity marking 1
Max. operating frequency 100 Hz / 5 kHz r UL 508
(switchable via DIP switch) r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
Response time (T 10-90 ) < 3.5 ms / < 100 μs Shipbuilding g
Transmission error ≤ 0.1 % of the full scale value Accessories see pages 226 … 236
Temperature coefficient ≤ 0.01 % /K
Zero/span adjustment ± 3% of upper range value