Page 114 - Apollo - Commercial Products Catalog
P. 114

BACKFLOW PREVENTERS





             DUCLF-4A SERIES                         DUAL CHECK VALVE
                                                     The Apollo DUCLF-4A Series Dual Check Valve Backflow Preventer is designed
                                                     to prevent cross-connections of non-potable water (non-hazardous) into safe
                                                     drinking water systems. It is a compact and economical device that consists
                                                     of two independently-acting, spring-loaded check valves in a corrosion-
                                                     resistant material.
                                                     FEATURES
                                                     •  Low Head Loss                 •  Maximum Working Pressure 175 psi
                                                     •  Independently-acting Check    •   Operating Temperature Range
                                                        Valves                           33°F-180°F
                                                     •  Compact and Lightweight       •   ASSE1024
                                                     •  Corrosion Resistant           •   CSA B64.6
                  Dimensions (In.) – Weight (Lbs.)   •  Replaceable Check Modules     •  5 year, domestic warranty
                                                     •  Industry Lay Lengths
                                                     •  Available in Standard and Swivel
                                                        Types














             DUC 4FP SERIES                          FIRE PROTECTION DUAL CHECK VALVE
                                                     The Apollo DUC 4FP Series Dual Check Backflow Preventer for Residential
                                                     Fire Sprinkler Systems prevents backflow by either backpressure or
                                                     backsiphonage from a cross-connection between potable water lines and
                                                     substances that are objectionable, but not health-hazards.
                                                     FEATURES
                                                     •  Low Pressure Loss             •  Maximum Supply Pressure 175 psi
                                                     •  Corrosion Resistant           •  Temperature Range 33°F - 180°F
                                                     •  Replaceable Check Modules     •  ASSE 1024
                                                     •  Pressure drop at 30 gpm is less   •   UL Classified
                                                        than 6 psi                    •   CSA B64.6
                                                     •  Complies with NFPA Standard 13D   •  Made in the USA
                                                     •  5 year, domestic warranty























          114
                                                           Customer Service (704) 841-6000       www.apollovalves.com