        Description and Handling
    1 218 Series
    80
















        Terminating stranded conductors in confined spaces   Terminating 0.75 mm  / 18 AWG conductors is possible;   Testing directly on the clamping spring.
                                                       2
        requires a great deal of patience, unless you use the new   however insulation diameter allows only every other
        218 Series terminal strips. The clamping units of these   clamping unit to be terminated with this conductor size.
        strips can be held open during termination process via
        integrated locking slide.















        Incorrect — Do not operate the locking slides from the
        back.



















        Conductor termination: To momentarily open clamping
        unit, use screwdriver and then insert stripped conductor.
        To open clamping unit for extended period, move locking
        slide toward conductor entry hole. Then fully insert
        stripped conductor and move locking slide back to original
        position (also possible to perform with fingernail).
















        Insulating housings available in different colors.  Marking via self-adhesive strips or ...  ... factory direct printing.

                        CAGE CLAMP  termi-
                                 ®
                        nates the following
                        copper conductors:*                                                    fine-stranded,
                                                                                               also with tinned
                        solid                              stranded                            single strands
        * For aluminum conductors, see notes in Section 13.