Page 128 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 128
128 Inverter System & Power Supply Unit
8.2 General Characteristics
Line voltage: 3x230 Vac -10% ... 500 Vac +10%, Standard supply configuration
selectable via dip switch (versions -4)
Regulation:
3x230 Vac -10% ... 690 Vac +10%, • 1 digital input (Enable)
selectable via dip-switch (versions -6)
SMB200 • 3-phase AC/DC Power Supply Unit
ADV200 - 4 • Basic
• 2 digital outputs: MLP signal (sum of the undervoltage limit
Line frequency: 50Hz or 60Hz (selectable via dip- set and the precharge) and ML signal (line voltage monitoring)
switch), ±5% • 1 relay output: 1 contact for “SMB” OK (normally open,
closed after precharging).
Power ratings: from 844 kW ... 6.2 MW (ver. -4)
from 930 kW ... 8.6 MW (ver. -6)
Options
Rated voltage DC link Supply voltage VLN x 1.35
• Input inductance (LR3-.-FFE, required)
THD ≤ 40% • Parallel connection M/S communication cable.
Overload 150% for 60 sec every 5 minutes (Heavy duty) or
110% for 60 sec every 5 minutes (Light duty) Conformity
IP20 protection degree (housing) excluding higher and lower Climatic conditions EN 60721-3-3 class 3K3,
power connections, where protection degree is IP00 (as per EN 60068-2-2
EN 60529).
Electrical safety EN 50178, EN 61800-5-1
Vibrations EN 60068-2-6, test Fc.,
EN 60721-3-3 class 3M1
EMC Immunity: EN61800-3, according to
environment;
Conducted emissions: EN 61800-3,
class C3
Environmental conditions
Ambient temperature: -10°C ... +40°C (+14°F ...+104°F),
40°C…+50°C (+104°F…+122°F)
with derating
Altitude: Max 4000 m a.s.l. (up to 2000 m
without derating)
Markings
Complies with the EEC directive
concerning low voltage equipment
Complies with directives for the
American and Canadian market.
(only with supply voltage ≤ 600Vac).
(pending)
.
C+
D-
ADV200 DC ADV200 DC ADV200 DC BUy
SMB200
Braking Resistor