Page 32 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 32

32                                 Inverter System & Power Supply Unit





          2.3	 Standard	connections




                 F1
                   1  3
      ADV200 - 4 • Basic
      ADV200-DC • DC bus power supply
                                                                                    (**)
               K1M                                                                 OK Relay
                   2  4                                                             (70-72)
                                                           Drive OK  Drive ready  K2  K1M            K0
                                   (*)
                    C  D                                R11 R14 R21 R24  12  11  10  9  8  7  C2  C3  S3
                                                      RS 485         Fault reset src  Multi ref sel 1 src  Multi ref sel 0 src  FR reverse mon  FR start mon  Digital input E mon  COM ID  0 V24  + 24V
                                                         Dig. Output 1  (Relay 1)  Dig. Output 2  (Relay 2)  (Enable)



                                                                                     Analog  output 2  Analog  output 1
                                                       Analog input 2  Analog input 1          COM Dig. Out.3/4
                                                EXP-DE-...  (optional)
                                  SMPS                                     0 V 10  + 10 V  - 10 V  Dig. Out.3  PS Dig. Out.3/4  Dig. Out.4

                                                       4 -  +  3  -  2  +  1  C1  S1+  S1-  6  C1  5  IC1  13  IS1 14
               G1   U  V  W  C  D



                                                                                  Standard connections and default drive configura-
                     M                                                                                      tion.
                    3~                                                                             (*) Fan connections:
                                                                                    3 x 400V / 50Hz, 1.15Arms ... 3 x 460V /
                                                                                                     60Hz, 1.4Arms
                                                                                          73150 ... 73550: 3 x 400V / 50Hz,
                     E                                                                                  1.55Arms
                                                                                              or 3 x 460V / 60Hz, 1.7Arms
                        M1
                                                                                           (**): Only for sizes ≥ ADV71600.







                                                F12
                                                               U
                                                     C                  M1
                                                               V
                                                     D  ADV200 (1)  W   3


                                                F22
                                                               U
                                                     C                  M2
                                                               V
                                  AFE200, SMB, SM32  D  ADV200 (2)  W   3
                                  or DC Power supply
                (3ph -
                      F1
                  L1
                400 VAC
                  L2
                  L3
                / 460 VAC,
                                 L1
                          K1M                   F32            U
                                                     C                  M3
                                                               V
                50/60 Hz)
                                                     D  ADV200 (3)  W   3
                                                                                  Connection of multi-drive on common DC bus with
                                                                                       AC/DC power supply unit (with pre-load).
                                                                                 For size 7 only, Adaptation for internal mounting of
                                                                                         "F...2--F.." fuses (DC side) on request
                                                F..2
                                                               U
                                                     C                  M..         Caution: To avoid to damage the internal EMI
                                                               V                  filter, regenerative converters may not supply the
                                                     D  ADV200 (..)  W  3         DC power supply to standard ADV drives, version
                                                                                         ADV....-DC or ADV...-IT must be used.
   27   28   29   30   31   32   33   34   35   36   37