Page 76 - Wieland - revos Industrial multipole connectors
P. 76
revos power
690 V 82 A + 400 V 16A
Contact inserts, screw connection
Contact inserts revos power Description Type Part No. P.U.
M D t Contact inserts revos power 4-/2-pole + ground 72.215.0653.0 10
POW STS 4/2 FA DB AG
Male insert
Female insert POW BUS 4/2 FA DB AG 72.205.0653.0 10
4-/2-pole + ground Technical data 690 V and 400 V
Rated voltage
690/400 V Rated voltage according to UL/CSA 600 V
Size 16 Rated impulse voltage 8 kV / 6 kV
Rated current 4 Contacts 82 A (CSA 70 A) / 2 Contacts 16 A
Degree of pollution 3
Rated cross section
EN 60999 4 x 6 – 16 mm and 2 x 1 – 2.5 mm 2
2
UL 4 x 10 – 4 AWG and 2 x 16 – 12 AWG
CSA 4 x 10 – 4 AWG and 2 x 16 – 12 AWG
Contacts
Material Copper alloy
Surface >16 A Ag / 16 A Sn
Insulation strip length 15 mm / 9 mm
Contact resistance ≤ 1.5 mΩ
Mating cycles 200
Screws head design / recomm. torque
Mounting screws H1 / 0.5 – 0.7 Nm
Clamping screws 4 x M6 / 1.2 – 1.6 Nm / 2 x H1 / 0.5 – 0.7 Nm
Ground conductor screws M5 / 2.0 – 2.5 Nm
Temperature range -40 … +120 °C
Housing revos basic Type Page
Hood, Size 16H 164, 174, 176
Hood, Size 16XL 177
Open-bottom base, Size 16 166, 178
Closed-bottom base, Size 16H 168, 180
Dimensions
4-/2-pole + ground 690/400 V
Derating curve
according to IEC 60512 sec. 3
Current carrying capability [A] Upper temperature limit
72.205/215.0653.0 revos power
4+2-pole 690 V / 400 V
2
82 A / 16 A / 16.0 mm / 2.5 mm 2
Corrected current AC [A]
Ambient temperature [°C]