Page 7 - Wieland - Circuit breakers
P. 7

selos
    Thermal-Magnetic Circuit Breakers
    Technical Data

    selos





          Max Voltage

                  Branch       480 Vac (PH-PH)
                               277 Vac (Ph - Gnd). for 0.2 - 32 A  / 240 Vac for 33 to 63 A
                               Self certified for 48 Vdc.


             Supplemental      480 Vac (PH-PH) / 277 Vac (Ph - Gnd).
                               Self certified for 48 Vdc



                               14 AWG – 4A WG @ 2.0 Nm (17.5 in lb)
             Wire Size         8 AWG – 3 AWG @ 2.8 Nm (25 in lb)

                               0.5 - 63 A, other sized available on request
            Amperage


            Approvals          cULus
                  Branch       cURus for general purpose
             Supplemental      cULus per UL508 for motor controllers.
                               -25 to 60
          Temperature          IP20
             IP Rating         100 000 cycles
       Mechanical life         6000 cycles
          Electrical life      3 G / 8-50 Hz
         Max Vibration
     Interrupt Ratings         10kA  for 0.5 - 63 A
                  Branch       10kA  for 0.5 - 6 A
             Supplemental      5kA  for 7 - 63 A, without fuse
                               10kA  for 7 - 63 A, with fuse



          Dimensions


























                                                                                                        Subject to change without notice