Page 63 - Critical Control flipbook_Neat
P. 63

Liquid Fuel Fire











           1    What is the name of the       2    What are its specific objectives related to the Priority Unwanted
                critical control for Liquid
                                                   Event (PUE)?
                Fuel Fire?
          Early detection of creeping failures  Proactively detect early causes of creeping failure by carrying out regular inspection,
                                             testing and maintenance and decrease the likelihood of incidents


           3    What are the critical         4    What are the activities       5    What can be sampled from
                                                                                      the set of activities for
                                                   within the management
                control performance
                requirements to meet the           systems that support               verification, providing a
                objectives?                        having the critical control        clear image of the critical
                                                   able to do what is required?       control status?
          Regular inspection for leaks around fuel   Scheduled preventative maintenance   Frequency of inspection and number of
          systems (storage vessels, bunds/dikes,   and inspection walkaround in CMMS   findings
          pump, pipeworks, flanges)          Report deviation/failure as near miss on   Number of iCare reports on detected
                                             iCare                              leaks
                                                                                Field verification of installation for visible
                                                                                leaks

          NDT Testing on storage vessels, pipework   Written scheme of NDT testing/piping   Evidence of NDT tests, thickness
          elbow/bends to identify erosion or   specificaiton                    measurements and findings
          thickness reduction                NDT Testing are in CMMS schedule   Overdue NDT tests in CMMS
          Flexible hoses are maintained as per the   DSCQP thinckess and corrosion   List of assets/equipment at risk
          manufacture’s instruction          measurement
                                             Flexi hose register with maintenance
                                             records

          Prevent pump seal/gasket failure by   Preventive Maintenance Routines are   Pump/seal selection according to the fuel
          having a preventive maintenance    schedule on CMMS                   Number of reported pump seal leaks
          routine. If low flash point fuel is used   Report deviation/failure as near miss on
          then double seals or magnetic drive   iCare
          pumps
                                             Pump and seal selection in maintenance
                                             instruction/work order

           6    What is the target performance for critical     7    What is the critical control performance
                                                                     trigger for shutdown, critical control review or
                control?
                                                                     investigation?

          Changes in fuel or fuel specification are addressed by a manage-  Management of Change process not followed for change in fuel/
          ment of change process. Creeping failures are detected early by   specification
          having a robust inspection and maintenance program   Assets/Equipment that is at risk of leakage due to decreased
                                                               thickness (below safe operating level)
                                                               ACert pre-qualification process not followed on AFR


















          Creation date: 01/2021 • The latest and only controlled version of this document is available on the HSE intranet.