Page 3 - Cannon Cool Rear Door Cooling Unit
P. 3







TITLE


Depth
Width
Height
Colour
Weight
DC0652
Refrigerant
Noise Level
Power Supply
Characteristics
Hot Swap Fan
Water Flow Rate
Cooling Capacity
Water Temp Flow
*Data center /Room conditions:
Water Temp Return
Remote monitoring
Electrical Connection
Air Temperature Range
Max. Power consumption
Air Flow Rate (closed loop)
Water connections (via base)
Typical Power consumption (75%)
Temperature/Humidity sensors
Hydraulic Circuit Max. Pressure
ƒF
3 of 8
ƒF
30 L/min
Rear Door Cooling Unit
(see install and maintenance manual for full room preparation).
1250 mm
to avoid excess condensate causing the WIRC to send alarms.
~
3/4" BSPP.
ñ
1 water in & 1 water out
IEC C14 inlet,
Water / Glycol,
1
800mm (19" mounting)
375W, (10W minimum).
100-240 Vac ~ 47 - 63Hz
ƒ& ¦ RI KHDW ORDG
Cabinet Mounted Rear Door
RAL 9002 Grey / 9005 Black
G% $ ¦ RI KHDW ORDG
1359 - 4077 m /h (800-2400 cfm)
TO 3M PVC TUBE.)
Rear Door Cooling Unit
Water /Air Cooling Unit
215kg (dry weight) 226kg (wet)
500W full load, (auto soft start).
Cannon Cool
4 off hot swap 48v dc fan cassettes
20% mix recomended
Air-Water Heat Exchanger Specification
11off temperature sensors 4 air @ front,4 air @ rear ,1 humidity
(6MM CONDENSATE DRAIN,
3M -LSOH cable, (240-110)
6 bar, nominal 2 bar. (0.5 bar pressure drop)
0 - 10 Kw * depending on data center conditions
47U with 42U usable 19" equipment space
Remote Monitoring control and snmp alarms via Cannon Guard option
10/01/11
monitor temperature and humidity and provide feedback via snmp, Keeping your data center or Cannon cabinet humidity levels
WIRC is an air to water heat exchanger and does not regulate humidity; it is recommended that external dehumidifier / humidifier
Humidity is directly related to the temperature, so monitoring temperature and humidity together is critical.The Cannon WIRC will
for system reliability(please note individual server manufactures recommendations vary for humidity & temperature) .The Cannon
system be in place to manage humidity within the data center or room. These parameters must be achieved before system Start up