Page 5 - Cannon Cool Rear Door Cooling Unit
P. 5




*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
TITLE
DC0652
Leak detection:-
heat load in cabinet.
Noise levels:- ('A' rating in dB)
'summing' control of water flow.
(V & A) from two optional PDU's.
5 of 8
Rear Door Cooling Unit

± : YDULDEOH VSHHG VRIW VWDUW IDQ ORDG
1


60dB with doors open @ min speed (3M/s air velocity)
52dB with doors closed @ min speed (3M/s air velocity)
72dB with doors closed at Max speed (9.5M/s air velocity)
Flow:- 40 Litres / Minute, 0.4 bar pressure drop @ 40L/min.
Relay interface to BMS system to control dampers and valves.
Control system:- CannonGuard environmental control system.
Rear Door Cooling Unit
6mm condensate drain push fit connection, pressure of 0.1 bar.
Water /Air Cooling Unit
Cannon Cool
[ 3:0 IDQV 9GF : 530 Pñ K KUV
/&' :DON E\ GLVSOD\ ± VKRZV FDELQHW ,' WHPSHUDWXUH KXPLGLW\
Fans:- 48Vdc , SELV. Class II PSU / 110 - 230Vac ,500W max load.
:DWHU ´ %63 KRVH FRQQHFWLRQV 0 IOH[LEOH KRVHV WR VKXW YDOYHV
Cooling system Technical specifications
Optional under floor water detection system with local and remote alarms.
4 'Zones' in cabinet, front and rear with independent control of fan speed and
15Kw single coil large bore air / water heat exchanger. 0.5 bar differential max.
Optional flow / water pressure meters with cross check for early leak detection.
Automatic control of fan speed and optional flow control of water dependant on
Optional electronic keypad lock with Keypad entry and optional remote operation.
10/01/11
Also shows temperature sensors (4 zones + water) front and rear and the power data
   1   2   3   4   5   6   7   8