DATA CAMP US

                                                                          A D V A NCE D  C O O L I NG  S CI E NCE




        STATE OF THE ART COOLING TECHNOLOGY

        Cannon Data Campus operates with advanced cooling
        technology, which combines two cutting edge, highly efficient
        systems to provide optimised PUE.
        ECONOMICAL FREE COOLING CHILLERS

        Drawing maximum free cooling benefit from available ambient
        air, reducing chiller run time and saving energy consumption.

        ‘IT’ EQUIPMENT IS NOT PHYSICALLY CONTAMINATED
        Importantly, ambient fresh air is used for Free Cooling but this
        external air is not required to enter the Data Hall, therefore no
        contamination by poor quality external air of sensitive server
        and switch equipment is possible.
        This hygienic feature prolongs the life of mission critical ‘IT‘
        infrastructure and reinforces resilience; an invaluable benefit.
        ‘CANNON COOL’ WITH-IN -ROW COOLING UNITS
        Cannon Cool With-In-Row Cooling (WIRC) Units substantially
        improve cooling efficiency within the Data Hall, benefiting from
        the close coupled air flow which avoids the need for long
        ducting runs or the large powerful fan systems normally                              Integrated Within-Row
        required to move air through complex ducting, over extended                        cooling provides direct aisle
                                                                                           cooling for energy efficiency
        distance.                                                                               and cost saving
        Space is also saved by the avoidance of such large ducting
        systems, or air plenums.
        QUIET, HIGH VOLUME AIR FLOW

        The six large, hot swappable radial blowers equipping each
        ‘Cannon Cool’ are quiet and efficient, consuming only 600w at
        100% and <100w at 25% load. 30kw max provides 25kw of
        sensible cooling when used with chilled water at 12°C.

        EFFICIENT – WATER BASED FREE COOLING MODE
        Coupled with modern, high efficiency Chilled water plant,
        compatible ambient conditions and free cooling coils a cooling
        PUE of under 1.06 is possible. (#1)
        DX: If a Direct Exchange ‘DX Gas’ system is desired rather than
        water then multiple 25kw units can provide 18kw of sensible
        cooling coupled to suitable external heat exchangers (#2) (No
        Free Cooling).
        AIR SIDE ECONOMISERS / FLOOD COOLING / FRESH AIR

        Optionally the Cannon MDC hall may be built to encompass
        large scale air handling systems with diverse free cooling. Air                     Cannon’s cable raceway
        may be delivered both under and over floor into the cold aisles.                     dramatically reduces
        The hot exhaust air being removed by overhead ductwork,                               installation costs.
        chimneys and low energy fans.



         (#1) 8 x WIRC units @ 500w = 4kw, 3kw of water pumps and 5kw of free cooler fan energy = 212kw total for 200kw of sensible cooling – (free cooling metric based
         on Southampton UK Winter period).
         (#2) External DX heat exchanger must be within 70m of the WIRC DX air handler and <15M above or below.