Building Services

         Console TYPE 38/40


         • Galvanised, assembly-ready cantilever bracket
         • Robot-controlled precision welding – highest safety and stability
         • Good adaptation to structural requirements thanks to graduated
           lengths
         • The mounting holes in the base plate are punched slots at 90° to
           each other, to improve ease of installation
         • Also suitable for fixing to ceilings
         Areas of application:
         • Projecting support structures for pipe sections, fittings, cable racks,
           pumps, ventilation ducts, ventilation units and air-conditioning units




          Article No.  Article Description             QTY
          8547 200    CONSOLE GAL.TYPE 38/40   200MM   e 10
          8547 350    CONSOLE GAL.TYPE 38/40   350MM   e 20
          8547 450    CONSOLE GAL.TYPE 38/40   450MM   e 10
          8547 600    CONSOLE GAL.TYPE 38/40   600MM    e 5
          8547 700    CONSOLE GAL.TYPE 38/40   700MM    e 5
          8547 1000   CONSOLE GAL.TYPE 38/40  1000MM    1 ü

                          Load values in Newton (N) for console TYPE 38/40
                               F                     F          F  A F          A F  A F  A F
                             A   A            A   A            A    A                 A
           Length  projection  mm  Total  length  mm  F = single load  F = single load  F = single load  F = single load  Distributed load
                                                                                                     L
                                                                                   L
                                                                  L
                                                 L
                               L
                                            A = L
                                                             A = 1/3 × L
                                                                              A = 1/4 × L
                          A = 1/2 × L
          200     206                 3.828            1.914            1.914             1.276            3.828
          350     356                 2.128            1.064            1.064              710             2.128
          450     456                 1.655              868              868              578             1.736
          600     606                 1.265              572              633              422             1.144
          700     706                 1.081              418              540              360              836
          1.000   1.006                640               200              300              194              398





































         When calculating the load-bearing capacity values, the permissible steel stress of 160 N/mm² and the maximum deflection of L/150 are not exceeded.
         The loads indicated only apply to the console.
         The other design parts must be tested for their permissible maximum load too.


     Technical data subject to change.