Page 46 - Icon Ridge Sanitary-Heating-Air Catalog
P. 46

Building Services

         Console with Support Type 41/41 STRUT


         Cantilever bracket with support for fixing to walls
         • Hot-dip galvanised
         Product benefits:
         • The mounting holes are punched slots at 90° to each other, to improve
           ease of installation
         • Sides bent inwards with teeth for extra hold
         Areas of application:
         • Projecting support structures for pipe sections, fittings, cable racks,
           pumps, ventilation ducts, ventilation units and air-conditioning units

          Article No.  Article Description             QTY
          8572 4141 600 1  CONSO.STRUT HD-GAL.41/41 600MM  1


                 Load values in Newton (N) for console TYPE 41/41
                          F
                    A   A
                                            L
           Length  Konsole  mm  F = single load  Distributed load
                      L
                 A = L
             600                 1.400                3.700












          Console Doubled STRUT

          Doubled cantilever bracket for fixing to walls
          • High quality galvanisation 8 – 10 μ
          • Fire tested
          Product benefits:                                                                         Fire-tested
          • The mounting holes are punched slots at 90° to each other, to improve
           ease of installation
          • Sides bent inwards with teeth for extra hold
          Areas of application:
          • Projecting support structures for pipe sections, fittings, cable racks,
           pumps, ventilation ducts, ventilation units and air-conditioning units

          Article No.  Article Description             QTY
          8573 4141 450  CONSO.STRUTD GAL.41/41  450MM  e 8
          8573 4141 600  CONSO.STRUTD GAL.41/41  600MM  1 v
          8573 4141 750  CONSO.STRUTD GAL.41/41  750MM  1 v
          8573 4141 1000  CONSO.STRUTD GAL.41/41 1000MM  1


                 Load values in Newton (N) for console TYPE 41/21
                          F
                    A   A
           Length  Konsole  mm  F = single load  Distributed load
                                            L
                       L
                 A = L
             450                 3.167                6.335
             600                 2.375                4.751
             750                 2.036                4.072
            1.000                1.049                2.796





         The loads indicated only apply to the console.
         The other design parts must be tested for their permissible maximum load too.


     Technical data subject to change.
     Availability subject to country specific rules and regulations.   www.iconridge.com   Source: Theo Förch GmbH & Co. KG           46