8.2.5. SM Measurement Data
Address Alert Notes
37056 G1 Measurement Status The measurement status for G1:
0 = No data is available
1 = OK
2 = Signal is clipped
37057 G1 Measurement Quality The measurement quality for G1:
0 = No data is available
1 = No Alert detected
3 = Low-Current Alert detected
5 = High-Current Alert detected
37058 G1 Measured Current The measured current from G1 in RMS.
This is a float value.
37060 G1 Measured Current The measured current from G1 in peak-to-
peak.
This is a float value.
37062 GV Measurement Status The measurement status for GV:
0 = No data is available
1 = OK
2 = Signal is clipped
37063 GV Measurement Quality The measurement quality for GV:
0 = No data is available
1 = No Alert detected
5 = High-Current Alert detected
37064 GV Measured Current The measured current from GV in RMS.
This is a float value.
37066 GV Measured Current The measured current from GV in peak-to-
peak.
This is a float value.
37118 G2 Measurement Status The measurement status for G2:
0 = No data is available
1 = OK
2 = Signal is clipped
37119 G2 Measurement Quality The measurement quality for G2:
0 = No data is available
1 = No Alert detected
3 = Low-Current Alert detected
5 = High-Current Alert detected
37120 G2 Measured Current The measured current from G2 in RMS.
This is a float value.
37122 G2 Measured Current The measured current from G2 in peak-to-
peak.
This is a float value.