 ST. JEROME’S CATHOLIC SCHOOL: ELECTRICAL SYSTEMS 1.0 POWER
.1 Main Service
Power to the school is obtained from a pad mounted transformer. The secondary feeders are routed underground from the pad location to the main distribution centre that is located in the electrical room, located on the main floor. The main distribution centre is the product of Eaton and was installed in 2017 when the school underwent a major modernization. It is rated at 1200A, 120/208V, 3-phase, 4-wire and is complete with a 1200A, 3P main breaker and feeder breakers of various sizes that feed various loads throughout the school. The main distribution centre has some spare breaker capacity available
COMMENTS: The main distribution centre is in good condition. The average life cycle of this equipment is 40 years, and should be good till 2057. No action is necessary.
.2 Breaker Panels
Branch circuit breaker panels that are fed from the main distribution centre have been provided throughout the school and are located in strategic locations to provide power to the lighting and other loads in the respective area. The breaker panels were installed in 2017 as part of the school modernization. Most panels have spare spaces available for the addition of future loads, if need be.
COMMENTS: The breaker panels are in good condition and no action is necessary, as breakers for these panels will be available well into the future.
2.0 MOTOR CONTROL .1 Motor Starters
Wall mounted motor starters have been provided in the mechanical room, located in the penthouse. These starters control the motors for mechanical equipment. Starters are the product of Seimens and are complete with hand-off-auto selector switches and pilot lights.
COMMENTS: Motor starters are in acceptable condition and no action is 3.0 LIGHTING
necessary.