Page 28 - EASA_AR100-2015_0815 APEX_IESCO_Neat
P. 28

Appendix, Page 2                            EASA AR100-2020 Recommended Practice - Rev. August 2020


            A.4.4  Disconnect                                 A.4.6  Leads
              A means for disconnecting the line-side power sup-  Test leads and insulated clips should be of adequate
            ply to the test panel should be located within sight   ampacity and voltage class for the machine being
            from the test panel.                              tested.
            A.4.5  Safety Switch                              A.5    High-Potential Ground (Earth) Test
 DRAFT
              An emergency hand or foot operated switch or      AC or DC high-potential testing current should be
            push button to de-energize the power source should   limited by impedance or instantaneous trips to limit
            be located in the test area. A remote emergency safety   damage when breakdown occurs.
            switch adjacent to the test area also is  recommended.