Page 28 - EASA_AR100-2015_0815 APEX_IESCO
P. 28

Appendix, Page 2                            EASA AR100-2015 Recommended Practice - Rev. August 2015


            supply to the test panel should be located within   A.4.6  Leads
            sight from the test panel.                          Test leads and insulated clips should be of ad-
                                                              equate ampacity and voltage class for the machine
            A.4.5  Safety Switch
              An emergency hand or foot operated switch or    being tested.
            push button to de-energize the power source should   A.5   High-Potential Ground (Earth) Test
            be located in the test area. A remote emergency     AC or DC high-potential testing current should
            safety  switch  adjacent  to  the  test  area  also  is   be limited by impedance or instantaneous trips to
              recommended.                                    limit damage when breakdown occurs.






































































            24