Page 4 - Appendix D - Emergency Lighting
P. 4
l) Near (see Note 1) manual release controls provided to release electronically
locked doors as recommended in BS 7273-4.
NOTE 1 For the purpose of this sub clause, “near” is normally considered to be within 2m
measured horizontally.
NOTE 2 For the purpose of this sub clause, “at” means that the emergency luminaire would
illuminate in both directions at the change of direction or intersection.
Emergency lighting should be provided so that each room (Open area) and escape route
has visible light from at least two emergency luminaries.
It must also be installed in areas where there is a lack of ambient or secondary lighting and
the failure of normal lighting through loss of power would reduce relevant lux levels below
those recommended within the standard, including:
a) All toilet facilities provided for those with a disability;
b) Any area >8m2 should be treated as an open area;
c) Multiple closet facilities without borrowed light;
d) Plant rooms, generator rooms, control rooms and switch rooms;
e) Adjacent to main control equipment associated with the provision of normal and
emergency lighting to the building;
f) Evacuation lift cars;
Lights to be either integrated ceiling grid lighting, stand-alone bulk head units, batten or
pendant lighting units. The use of twin spot floodlights should be avoided internally as direct
spot lights can cause disability glare.
All emergency lighting must be installed with suitable testing facilities.
A competent and qualified electrical contractor must be employed to design, install, test and
commission the system.
Location Minimum Lux level Duration Reference Plane
Treatment rooms 50lx 30 minutes Horizontal on working
plane
First Aid Rooms 15lx 30 minutes Horizontal on working
plane
Kitchens 15lx 30 minutes Horizontal on working
plane, switches and
cut-outs readily visible
Reception areas 15lx Full duration In plane of visual task
Plant / switch rooms 15lx Full duration In plane of visual task
Fire Alarm control 15lx Full duration In plane of visual task
Refuges 5lx Full duration Horizontal on floor,
vertical at wall-
mounted
communication
devices and sign
Document Classification Final Document Ref: 3.1-RCS-RHSE-(800)-268 Version 1.1
4