Page 5 - Appendix D - Emergency Lighting
P. 5
Escape panic 5lx Full duration In plane of visual task
hardware
Fire Equipment 5lx Full duration In plane of visual task
Fire exit signs 5lx Full duration In plane of visual task
Escape routes 1lx Full duration Horizontal on floor
Rooms >60m2 0.5lx Full duration Horizontal on floor
Toilet / Change 0.5lx Full duration Horizontal on floor
Battery duration;
1 hour minimum duration (Autonomy) for emergency lighting:
Must fully recharge within 24 hours prior to full occupation
Premises must be evacuated immediately
3 hour duration for emergency lighting required for:
1
Sleeping risks (Hotels, HMO’s)
Licensed premises and places of entertainment
Premises requiring early occupation (Schools, Hospitals)
1
Note ;
Co-op minimum requirement for emergency lighting are stand-alone autonomous units with
a minimum 3 hour duration battery. The advantage of using 3 hour duration batteries where
1 hour is the minimum requirement, is that if the mains fails for just 1 hour, there is still 2
hours duration remaining in the batteries, allowing an immediate reoccupation of the
premises. If 1 hour duration is used, the batteries would have no remaining capacity and
would take up to 24 hours to recharge, thus delaying reoccupation of the premises.
For further information please see: MEP Data Sheet – 10 Emergency Lighting
Document Classification Final Document Ref: 3.1-RCS-RHSE-(800)-268 Version 1.1