Page 5 - Appendix D - Emergency Lighting
P. 5

Escape panic          5lx                   Full duration         In plane of visual task
                 hardware
                 Fire Equipment        5lx                   Full duration         In plane of visual task
                 Fire exit signs       5lx                   Full duration         In plane of visual task
                 Escape routes         1lx                   Full duration         Horizontal on floor
                 Rooms >60m2           0.5lx                 Full duration         Horizontal on floor
                 Toilet / Change       0.5lx                 Full duration         Horizontal on floor


               Battery duration;

               1 hour minimum duration (Autonomy) for emergency lighting:
                     Must fully recharge within 24 hours prior to full occupation
                     Premises must be evacuated immediately

                     3 hour  duration for emergency lighting required for:
                             1
                     Sleeping risks (Hotels, HMO’s)

                     Licensed premises and places of entertainment
                     Premises requiring early occupation (Schools, Hospitals)



                     1
               Note  ;
               Co-op minimum requirement for emergency lighting are stand-alone autonomous units with

               a minimum 3 hour duration battery. The advantage of using 3 hour duration batteries where
               1 hour is the minimum requirement, is that if the mains fails for just 1 hour, there is still 2
               hours duration remaining in the batteries, allowing an immediate reoccupation of the

               premises. If 1 hour duration is used, the batteries would have no remaining capacity and
               would take up to 24 hours to recharge, thus delaying reoccupation of the premises.




               For further information please see: MEP Data Sheet – 10 Emergency Lighting

























                 Document Classification    Final   Document Ref:   3.1-RCS-RHSE-(800)-268   Version   1.1