Page 269 - McD_6118-AEW-XX-XX-NBS-A-001_Neat
P. 269

560 EXISTING EDGE TRIMS
      • Fasteners: Check security. Replace as necessary.
      • Existing coverings: Cut out from edge trim recess sufficient to accommodate
          coatings.

565 EXISTING GUTTERS/ OUTLETS
      • Dirt, debris and build up of previous coverings/ coatings: Remove to restore free
          flow of water.

570 EXISTING CRACKS/ GAPS
      • General: Rake out, clean and make good with sealants or repair systems
          recommended by coating manufacturer.

575 FINAL POWER WASH TO EXISTING COVERINGS
      • General: Water jet clean all areas. Allow to dry.

580 STERILIZATION TREATMENT TO EXISTING COVERINGS
      • Preliminary work: Complete including making good and cleaning down.
      • Biocidal solution: Apply to all areas previously subject to organic growth. Allow to
          dry.

          NEW SUBSTRATES/ VAPOUR CONTROL LAYERS/ WARM DECK ROOF INSULATION

610 FIXING TIMBER TRIMS
      • Fasteners: Sherardized steel screws.
      • Fixing centres (maximum): 600 mm.

620 LAYING OVERLAY TO METAL DECK
      • Setting out: Lay boards with staggered joints and long edges at right angles to
          troughs in deck.
          - Joints: 1 mm per metre panel size.
          - End joints: Centred over crowns of deck.
      • Fasteners:
          - Type: As recommended for purpose by fastener manufacturer.
             Fixing centres: One fastener per crown along each long edge and at 300 mm
             centres along every alternate crown.
          - Fastener heads: Flush with, or below board surface.

630 LAYING VAPOUR CONTROL LAYER
      • Membrane: Loose laid, flat and without wrinkles.
      • Laps: Sealed using materials and method recommended by membrane
          manufacturer.
      • Upstands, kerbs and other penetrations: Enclose edges of insulation. Lap with
          coatings to form a complete seal.

RotF generic (intermediate) NBS 2014  6118-AEW-XX-XX-NBS-A-01