Drainage & Piped Services Standard Specification
Version 2014-1

Cold Water Supply System
System Performance: Design and detailing hot and cold water systems type A;
Cold water supply;
Standard: To BS 8558 or BS EN 806-2 and in accordance with HSE publication ‘The control of
legionella bacteria in water systems. Approved code of practice and guidance’.

Pipeline sizes for hot and cold water systems type A;
and Draw off requirements for hot and cold water systems type A.
Arrangement: Mains fed system
Water meters: Water meters.
Storage tank or cistern: Glass fibre insulated reinforced storage tank/booster set located in the
external refuse area - for compliance with water regulations
Water treatment plant: Magnetic water conditioners.
Pipelines:
Below ground: Polyethylene (PE) pipelines for water supply.
Above ground: Copper pipelines type B.
Pipeline accessories:
Accessories:
Valves:
Isolating valves: Stop valves to BS EN 1213
Check valves: To BS 6282-1.
Regulating valves: Constant flow regulator/Isolation valve.
Mixing valves: TMV3
Draining devices: Submit details
Accessories:
Thermal insulation:
Pipelines: Foil faced mineral wool internally with electrical resistance surface trace heating and
water proofing for external installations.
Tanks: Manufacturer applied.
Sanitary appliances:
Flush control devices: Solenoid valves
Controls: PIR controlled
Plant and equipment identification:
Execution: As manufactures recommendations.
System Completion:

System Performance

Design and detailing hot and cold water systems type A

Design: Complete the design and detailing of the hot and cold water supply.

Standard: To BS 8558 or BS EN 806-2 and in accordance with HSE publication ‘The control of
legionella bacteria in water systems. Approved code of practice and guidance’.