                    9.3.4.6.  If welding or flame cutting is done underground:
                (a)  timber supports and other combustible structures or materials should be protected
                    by a fireproof screen;
                (b)  suitable fire extinguishers should be kept readily available;
                (c)  a constant watch should be kept for outbreaks of fire;
                (d)  welding fumes should be removed by exhaust ventilation.



                9.3.5. Electricity

                    9.3.5.1.  Electrical  installations  in  shafts and tunnels should comply with the
                relevant national laws or regulations.
                    9.3.5.2.  Main switchgear  for cutting off the supply of  electricity  from  all
                underground installations should:
                (a)  be installed on the surface;
                (b)  be accessible only to authorised persons;
                (c)  be attended by a competent person authorised to operate it.

                    9.3.5.3.  Where necessary suitable lightning arresters should be installed on the
                surface to protect the installation below  ground  from  abnormal  voltage  due  to
                atmospheric electricity.

                    9.3.5.4.  The main cables supplying current to electric motors installed  in  the
                vicinity of shafts (such as those  for underground fans or drainage pumps)  should  be
                duplicated if the stopping of these motors would cause danger.
                    9.3.5.5.  All switches should be of the enclosed safety type.

                    9.3.5.6.  Fixed lamps underground should be provided  with a strong protective
                cover of glass or other transparent material or with a guard.
                    9.3.5.7.  Whenever  required  by  local conditions, lamp fittings should be proof
                against dust, gases and water.
                    9.3.5.8.  The voltage of hand lamps (portable  lamps)  used  underground  should
                not exceed extra-low safety voltage.


                9.3.6. Underground lighting

                    9.3.6.1.  All places where workers have to work or pass should be adequately lit.

                    9.3.6.2.  In addition to the main lighting, there should be emergency lighting that
                functions long enough to enable the workers to reach the surface safely.



                9.4.   Drilling

                    9.4.1.  When drilling is done in rock, loose rock should be scaled down to protect
                drillers against falls  of ground; where this is not practicable, a protective  canopy or
                overhead screen should be provided.