Page 239 - 2018_IFC
P. 239

CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS



                   ceiling finishes exposing the structure, unless  fied in Table 1103.1 as further enumerated in Sections 1104.2
                   there is an attic, crawl space or basement avail-  through 1104.25, and  the building code that  applied at  the
                   able that could provide access for interconnection  time of construction. Where the provisions of this chapter
                   without the removal of interior finishes.  conflict with the building code that applied at the time of con-
           1103.8.3 Power source. Single-station smoke alarms shall  struction, the most restrictive provision shall apply. Existing
           receive their primary power from the building wiring pro-  buildings that were not required to comply with a building
           vided that such wiring is served from a commercial source  code at the time of construction shall comply with the mini-
           and shall  be  equipped  with a battery backup. Smoke  mum egress requirements where specified in Table 1103.1 as
           alarms with integral strobes that are not equipped with bat-  further enumerated in Sections 1104.2 through 1104.25.
           tery backup shall be connected to an emergency electrical  1104.2 Elevators, escalators and moving walks. Elevators,
           system. Smoke alarms shall emit a signal when the batter-  escalators and moving walks shall not be used as a compo-
           ies are low. Wiring shall be permanent and without a dis-  nent of a required means of egress.
           connecting switch other than as required for overcurrent  Exceptions:
           protection.
                                                                   1. Elevators used as an  accessible means of egress
              Exceptions:                                            where allowed by Section 1009.4.
                1. Smoke alarms are permitted to be solely battery  2. Previously approved elevators, escalators and mov-
                   operated in existing buildings where construction  ing walks in existing buildings.
                   is not taking place.
                                                              1104.3 Exit sign illumination. Exit signs shall be internally
                2. Smoke alarms are permitted to be solely battery  or externally illuminated. The face of an exit sign illuminated
                   operated in buildings that are not served from a  from an external source  shall have  an  intensity of not less
                   commercial power source.                   than 5 foot-candles (54 lux). Internally illuminated signs shall
                3. Smoke alarms are permitted to be solely battery  provide equivalent luminance and be listed for the purpose.
                   operated in existing areas of buildings undergo-  Exception:  Approved  self-luminous signs that provide
                   ing alterations or repairs that do not result in the  evenly illuminated letters shall  have a minimum  lumi-
                   removal of interior walls or ceiling finishes  nance of 0.06 foot-lamberts (0.21 cd/m ).
                                                                                                2
                   exposing  the structure,  unless there is an attic,
                   crawl space or basement available that could pro-  1104.4 Power source.  Where emergency illumination is
                   vide access for  building wiring without the  required in Section 1104.5, exit signs shall be visible under
                   removal of interior finishes.              emergency illumination conditions.
                                                                 Exception: Approved signs that provide continuous illu-
         1103.9 Carbon monoxide alarms. Carbon monoxide alarms
         shall be installed in existing dwelling units and sleeping units  mination independent of external power sources  are not
         where those units include any of the conditions identified in  required to be connected to an emergency electrical sys-
         Sections  915.1.2 through 915.1.6.  The carbon monoxide  tem.
         alarms shall be installed in the locations specified in Section  1104.5 Illumination emergency power.  Where  means of
         915.2 and the installation shall be in accordance with Section  egress illumination is provided, the power supply for means
         915.4.                                               of egress  illumination shall normally be provided  by the
                                                              premises’ electrical supply. In the event of power supply fail-
           Exceptions:
                                                              ure,  illumination shall be automatically  provided from  an
              1. Carbon monoxide alarms are permitted to be solely  emergency system for the following occupancies where such
                battery operated where the code that was in effect at  occupancies require two or more means of egress:
                the time of construction did not require carbon mon-
                oxide detectors to be provided.                  1. Group A having 50 or more occupants.
                                                                     Exception:  Assembly occupancies used exclu-
              2. Carbon monoxide alarms are permitted to be solely
                battery operated in dwelling units that are not served  sively as a place of worship and having an occupant
                                                                     load of less than 300.
                from a commercial power source.
                                                                 2. Group B  buildings three  or more stories in height,
              3. A carbon monoxide detection system in accordance
                with Section 915.5 shall be an acceptable alternative  buildings with 100 or more occupants above or below a
                                                                   level of exit discharge serving the occupants or build-
                to carbon monoxide alarms.
                                                                   ings with 1,000 or more total occupants.
         1103.10 Medical gases. Medical gases stored and transferred
         in health-care-related facilities shall be  in accordance with  3. Group E in interior exit access and exit stairways and
                                                                   ramps, corridors, windowless areas with student occu-
         Chapter 53.
                                                                   pancy, shops and laboratories.
                                                                 4. Group F having more than 100 occupants.
                           SECTION 1104                              Exception: Buildings used only  during daylight
           MEANS OF EGRESS FOR EXISTING BUILDINGS                    hours and that are provided with windows for natu-
         1104.1 General.  Means of egress in existing buildings shall  ral light in accordance with the International Build-
         comply with the minimum egress requirements where speci-    ing Code.



         206                                                                        2018 INTERNATIONAL FIRE CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   234   235   236   237   238   239   240   241   242   243   244