Page 244 - 2018_IFC
P. 244

CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS



                       2. Twenty-three inches (584 mm) between a  1105.4 Incidental uses  in existing  Group I-2. Incidental
                         stepped aisle  handrail and  seating where  a  uses associated with and located within existing single-occu-
                         stepped  aisle does not  serve more  than five  pancy or mixed-occupancy Group I-2 buildings and that gen-
                         rows on one side.                        erally pose a greater level of risk to such occupancies shall
               3. Twenty inches (508 mm) between a stepped aisle hand-  comply with the provisions of Sections 1105.4.1 through
                  rail or guard and seating where the aisle is subdivided  1105.4.3.2.1. Incidental uses in Group I-2 occupancies are
                  by a mid-aisle handrail.                        limited to those listed in Table 1105.4.
               4. Forty-two inches (1067 mm) for level or ramped aisles  1105.4.1 Occupancy classification. Incidental uses shall
                  having seating on both sides.                      not be individually classified in accordance with Section
                                                                     302.1 of the International Building Code. Incidental uses
                    Exceptions:
                                                                     shall be included in the building occupancies within which
                       1. Thirty-six  inches (914 mm) where the  aisle  they are located.
                         serves fewer than 50 seats.
                                                                     1105.4.2 Area limitations. Incidental uses shall not
                       2. Thirty inches (760 mm) where the aisle serves  occupy more than 10 percent of the building area of the
                         fewer than 15 seats and does not serve as part  story in which they are located.
                         of an accessible route.
                                                                     1105.4.3 Separation and protection. The incidental uses
               5. Thirty-six inches (914 mm) for level or ramped aisles  listed in Table 1105.4 shall be separated from the remain-
                  having seating on only one side.                   der of the building or equipped with an automatic sprin-
                    Exception: Thirty inches (760 mm) for catchment  kler system, or both, in accordance with the provisions of
                    areas serving not more than 60 seats and not serving  that table.
                    as part of an accessible route.                    1105.4.3.1 Separation. Where Table 1105.4 specifies a
               6. In Group I-2, where aisles are used for movement of  fire-resistance-rated separation, the incidental uses
                  patients in beds,  aisles shall comply with Section  shall be separated from the remainder of the building in
                  1105.6.7.                                            accordance with Section 509.4.1 of the  International
                                                                       Building Code.
             1104.24  Stairway floor number  signs. Existing  stairways
             shall be marked in accordance with Section 1023.9.        1105.4.3.2 Protection. Where Table 1105.4 permits an
                                                                       automatic sprinkler  system without  a fire-resistance-
             1104.25 Egress path markings. Existing high-rise buildings
             of Group A, B, E, I, M and R-1 occupancies shall be provided  rated separation, the incidental uses shall be separated
             with luminous egress path markings in accordance with Sec-  from the remainder  of  the  building by construction
             tion 1025.                                                capable of resisting the passage of smoke in accordance
                                                                       with Section 509.4.2  of  the  International Building
               Exception: Open, unenclosed stairwells in historic build-  Code.
               ings designated as historic under a state or local historic
               preservation program.                                     1105.4.3.2.1 Protection limitation. Except as other-
                                                                         wise specified in Table 1105.4 for certain incidental
                                                                         uses, where an  automatic sprinkler system is  pro-
                               SECTION 1105                              vided  in  accordance with Table 1105.4, only  the
                     CONSTRUCTION REQUIREMENTS                           space occupied  by  the incidental use need be
                         FOR EXISTING GROUP I-2                          equipped with such a system.
             1105.1 General. Existing Group I-2 shall meet all of the fol-  1105.5 Corridor construction. In Group I-2, in areas hous-
             lowing requirements:                                 ing patient sleeping  or care rooms,  corridor walls and the
                                                                  opening protectives therein shall provide a barrier designed to
               1. The minimum fire safety requirements in Section 1103.
                                                                  resist the  passage of smoke in  accordance  with  Sections
               2. The minimum mean of egress requirements in Section  1105.5.1 through 1105.5.7.
                  1104.
                                                                     1105.5.1 Materials. The walls shall be of materials per-
               3. The additional egress and construction requirements in  mitted by the building type of construction.
                  Section 1105.
                                                                     1105.5.2 Fire-resistance  rating. Unless required else-
               Where the provisions of this chapter conflict with the con-  where in this code, corridor walls are not required to have
             struction requirements that applied at the time of construc-  a fire-resistance rating. Corridor walls that were installed
             tion, the most restrictive provision shall apply.       as fire-resistance-rated assemblies in accordance with the
             1105.2 Applicability.  The provisions of Sections 1105.3  applicable codes under  which  the building was con-
             through 1105.8, 1105.10 and 1105.11 shall apply to the exist-  structed, remodeled or altered shall be maintained unless
             ing Group I-2 fire area.                                modified in accordance with the  International Existing
                                                                     Building Code.
             1105.3 Construction. Group  I-2, Condition 2 shall not be
             located on a floor level higher than the floor level limitation
             in Table 1105.3 based on the type of construction.





             2018 INTERNATIONAL FIRE CODE ®                                                                      211
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   239   240   241   242   243   244   245   246   247   248   249