SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT



                           SECTION 907                           culated water flow rate as established in the equipment’s
                INCINERATORS AND CREMATORIES                     design specifications.
         907.1 General. Incinerators  and crematories shall be listed
         and labeled in accordance with UL 791 and shall be installed           SECTION 909
         in accordance with the manufacturer’s instructions.              VENTED WALL FURNACES
                                                              909.1  General.  Vented wall furnaces shall be installed in
                           SECTION 908                        accordance with their listing and the manufacturer’s instruc-
                 COOLING TOWERS, EVAPORATIVE                  tions.  Oil-fired  furnaces shall be tested in  accordance  with
                CONDENSERS AND FLUID COOLERS                  UL 730.
                                                              909.2 Location. Vented wall furnaces shall be located so as
         908.1 General. A cooling tower used in conjunction with an  not to cause a fire hazard to walls, floors, combustible fur-
         air-conditioning  appliance shall be installed in accordance  nishings or doors.  Vented wall furnaces installed between
         with  the manufacturer’s instructions. Factory-built cooling  bathrooms and adjoining rooms shall not circulate air from
         towers shall be listed in accordance with UL 1995.   bathrooms to other parts of the building.
         908.2  Access. Cooling towers, evaporative condensers and  909.3 Door swing. Vented wall furnaces shall be located so
         fluid coolers shall be provided with ready access.   that a door cannot swing within 12 inches (305 mm) of an air
         908.3 Location. Cooling towers, evaporative condensers and  inlet or air outlet of such furnace measured at right angles to
         fluid coolers shall be located to prevent the discharge vapor  the opening. Doorstops or door closers shall not be installed
         plumes from entering occupied spaces. Plume discharges  to obtain this clearance.
         shall be not less than 5 feet (1524 mm) above or 20 feet (6096  909.4 Ducts prohibited. Ducts shall not be attached to wall
         mm) away from any ventilation inlet to a building. Location  furnaces. Casing extension boots shall not be installed unless
         on the property shall be as required for buildings in accor-  listed as part of the appliance.
         dance with the International Building Code.
                                                              909.5 Manual shutoff valve. A manual shutoff valve shall be
         908.4 Support and anchorage. Supports for cooling towers,  installed ahead of all controls.
         evaporative condensers and fluid coolers shall be designed in  909.6 Access. Vented wall furnaces shall be provided with
         accordance with the  International  Building  Code. Seismic  access for cleaning of heating surfaces, removal of burners,
         restraints shall be as required by the International Building  replacement of sections, motors, controls, filters and other
         Code.                                                working parts, and for adjustments and lubrication of parts
         908.5  Water  supply. Cooling towers,  evaporative coolers  requiring such attention. Panels, grilles and access doors that
         and fluid coolers shall be provided with an approved water  must be removed for normal servicing operations shall not be
         supply, sized for peak demand. The quality of water shall be  attached to the building construction.
         provided in accordance with the equipment manufacturer’s
         recommendations. The piping system and protection of the               SECTION 910
         potable water supply system shall be installed as required by       FLOOR FURNACES
         the International Plumbing Code.
                                                              910.1  General. Floor furnaces  shall  be installed in accor-
         908.6 Drainage. Drains, overflows and blowdown provisions  dance with their listing and the manufacturer’s instructions.
         shall be indirectly connected to an approved disposal loca-  Oil-fired furnaces shall be tested in accordance with UL 729.
         tion. Discharge of chemical waste shall be approved by the
         appropriate regulatory authority.                    910.2 Placement. Floor furnaces shall not be installed in the
                                                              floor of any aisle or passageway of any auditorium, public
         908.7  Refrigerants  and  hazardous  fluids. Heat exchange  hall, place of assembly, or in any egress element from any
         equipment  that contains a  refrigerant and  that is part of a  such room or space.
         closed refrigeration system shall comply with Chapter 11.
         Heat exhange  equipment containing  heat transfer fluids  With the exception of wall register models, a floor furnace
         which are flammable, combustible or hazardous shall comply  shall not be placed closer than 6 inches (152 mm) to the near-
         with the International Fire Code.                    est wall, and wall register models shall not be placed closer
                                                              than 6 inches (152 mm) to a corner.
         908.8 Cooling towers. Cooling towers, both open circuit and
                                                                 The furnace shall be placed such that a drapery or similar
         closed circuit type, and evaporative condensers shall comply  combustible object will not be nearer than 12 inches (305
         with Sections 908.8.1 and 908.8.2.
                                                              mm) to any portion of the register of the furnace. Floor fur-
           908.8.1 Conductivity or flow-based control of cycles of  naces shall not be installed in concrete  floor construction
           concentration. Cooling towers and evaporative condens-  built on grade. The controlling thermostat for a floor furnace
           ers shall include controls that automate system bleed based  shall be located within the same room or space as the floor
           on conductivity, fraction  of metered makeup  volume,  furnace or shall be located in an adjacent room or space that
           metered bleed volume,  recirculating pump  run time  or  is permanently open to the room or space containing the floor
           bleed time.                                        furnace.
           908.8.2 Drift eliminators. Cooling towers  and evapora-  910.3 Bracing. The floor around the furnace shall be braced
           tive condensers  shall be equipped  with drift eliminators  and headed with a support framework design in accordance
           that have a maximum drift rate of 0.005 percent of the cir-  with the International Building Code.