Page 125 - 2018_IMC
P. 125

REFRIGERATION




           1105.6.1  Discharge  location. The  discharge of the  air  [F]  1105.9  Emergency  pressure  control  system. Perma-
           shall be to the outdoors in accordance with  Chapter 5.  nently installed refrigeration systems containing more than
           Exhaust from mechanical ventilation systems shall be dis-  6.6 pounds (3 kg) of flammable, toxic or highly toxic refrig-
           charged not less than 20 feet (6096 mm) from a property  erant or ammonia shall be provided with an emergency pres-
           line or openings into buildings.                   sure control system in accordance with Section 605.10 of the
              1105.6.1.1  Indoor  exhaust  opening  location. Indoor  International Fire Code.
              mechanical  exhaust intake openings shall be located
              where refrigerant leakage is likely to concentrate based          SECTION 1106
              on the refrigerant’s relative density to air, and the loca-  MACHINERY ROOM, SPECIAL REQUIREMENTS
              tions of the air current paths and refrigerating machin-
              ery.                                            1106.1  General.  Where required by Section 1104.2, the
                                                              machinery room shall meet the requirements of this section in
           1105.6.2  Makeup  air. Provisions shall be made for
           makeup air to replace that being exhausted. Openings for  addition to the requirements of Section 1105.
           makeup air shall be located to avoid intake of exhaust air.  1106.2  Elevated temperature.  There shall not be an open
           Supply and exhaust ducts to the machinery room shall not  flame-producing device or continuously operating hot surface
           serve any other area, shall be constructed in accordance  over 800°F (427°C) permanently installed in the room.
           with Chapter 5 and shall be covered with corrosion-resis-  1106.3 Ammonia room ventilation. Ventilation systems in
                                 1
           tant screen of not less than  / -inch (6.4 mm) mesh.  ammonia machinery rooms shall be operated continuously at
                                  4
           1105.6.3 Ventilation rate. For other than ammonia sys-  the ventilation rate specified in Section 1105.6.3.
           tems, the mechanical ventilation systems shall be capable  Exceptions:
           of exhausting the minimum quantity of air both at normal
           operating and emergency conditions, as required by Sec-  1. Machinery rooms equipped with a  vapor detector
           tions 1105.6.3.1 and 1105.6.3.2. The  minimum required    that will automatically start the ventilation system at
           emergency ventilation rate for  ammonia shall be 30 air   the ventilation rate specified in Section 1105.6.3,
           changes per hour in accordance with IIAR2. Multiple fans  and that will actuate an alarm at a detection level not
           or multispeed fans shall be allowed to produce the emer-  to exceed 1,000 ppm.
           gency ventilation rate and to obtain a reduced airflow for  2. Machinery rooms conforming to the Class 1, Divi-
           normal ventilation.                                       sion 2,  hazardous  location classification  require-
              1105.6.3.1  Quantity—normal  ventilation.  During      ments of NFPA 70.
              occupied conditions, the mechanical ventilation system  1106.4  Flammable  refrigerants.  Where refrigerants of
              shall exhaust the larger of the following:      Groups A2, A3, B2 and B3 are used, the  machinery  room
                                                              shall conform to the Class 1, Division 2, hazardous location
                1. Not less than 0.5  cfm per square foot (0.0025
                    3
                          2
                   m /s • m ) of  machinery  room  area  or 20 cfm  classification requirements of NFPA 70.
                          3
                   (0.009 m /s) per person.                      Exceptions:
                2. A volume required to limit the room temperature  1. Ammonia machinery rooms that are provided with
                   rise to 18°F (10°C) taking into account the ambi-  ventilation in accordance with Section 1106.3.
                   ent heating effect of all machinery in the room.  2. Machinery rooms for systems containing Group A2L
              1105.6.3.2  Quantity—emergency  conditions.  Upon      refrigerants  that are in accordance with  Section
              actuation of the refrigerant detector required in Section  1106.5.
              1105.3, the mechanical ventilation system shall exhaust  1106.5 Special requirements for Group A2L refrigerant
              air from the machinery room in the following quantity:  machinery rooms. Machinery rooms for systems containing
                                                              Group A2L refrigerants shall comply with Sections 1106.5.1
              Q =  100 ×  G                  (Equation 11-2)  through 1106.5.3.
              For SI: Q =  0.07 ×  G                             Exception: Machinery rooms conforming to the Class I,
                                                                 Division 2, hazardous location classification requirements
              where:                                             of NFPA 70  are  not required to comply with Sections
                                                  3
              Q = The airflow in cubic feet per minute (m /s).   1106.5.1 and 1106.5.2.
                                                                 [F] 1106.5.1 Refrigerant detection system. The machin-
              G = The design mass of refrigerant in pounds (kg) in
                   the largest system, any part of which is located in  ery  room shall be provided with a  refrigerant detection
                   the machinery room.                           system. The refrigerant detection system shall be in accor-
                                                                 dance with Section 605.8 of the International Fire Code
         1105.7  Termination  of  relief  devices.  Pressure relief  and all of the following:
         devices, fusible plugs and purge systems located within the  1. The detectors shall activate at or below a refrigerant
         machinery room shall terminate outside of the structure at a  concentration of 25% of the LFL.
         location not less than 15 feet (4572 mm) above the adjoining
         grade  level and not less than 20  feet  (6096 mm) from any  2. Upon activation, the detection system shall activate
         window, ventilation opening or exit.                        the emergency ventilation system required by Sec-
                                                                     tion 1106.5.2.
         1105.8  Ammonia  discharge.  Pressure relief valves for
         ammonia systems shall discharge  in accordance  with      3. The detection, signaling and control circuits shall be
         ASHRAE 15.                                                  supervised.

         108                                                                 2018 INTERNATIONAL MECHANICAL CODE 
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   120   121   122   123   124   125   126   127   128   129   130