REFRIGERATION




               1106.5.2 Emergency ventilation system. An emergency  1107.2  Piping  location.  Refrigerant piping that  crosses an
               ventilation system  shall be provided at  the  minimum  open space that affords passageway in any building shall be
               exhaust rate specified in ASHRAE 15 or Table 1106.5.2.  not less than 7 feet 3 inches (2210 mm) above the floor unless
               Shutdown of the emergency ventilation system shall be by  the piping is located against the ceiling of such space. Refrig-
               manual means.                                      erant piping shall not be placed in any of the following:
                                TABLE 1106.5.2                       1. A fire-resistance-rated exit access corridor.
                           MINIMUM EXHAUST RATES
                                                                     2. An interior exit stairway.
                REFRIGERANT        Q(m/sec)         Q(cfm)
                                                                     3. An interior exit ramp.
             R32                     15.4           32,600
                                                                     4. An exit passageway.
             R143                    13.6           28,700
                                                                     5. An elevator,  dumbwaiter or other shaft containing  a
             R444A                   6.46           13,700
                                                                       moving object.
             R444B                   10.6           22,400
                                                                     6. A shaft that has one or more openings into a fire-resis-
             R445A                   7.83           16,600
                                                                       tance-rated exit access corridor, interior exit stairway or
             R446A                   23.9           50,700
                                                                       ramp or exit passageway.
             R447A                   23.8           50,400
                                                                     1107.2.1  Piping  in  concrete  floors.  Refrigerant piping
             R451A                   7.04           15,000           installed in concrete floors shall be encased in pipe ducts.
             R451B                   7.05           15,000           The piping shall be isolated and supported to prevent dam-
             R1234yf                 7.80           16,600           aging vibration, stress and corrosion.
             R1234ze(E)              5.92           12,600           1107.2.2  Refrigerant  penetrations.  Refrigerant piping
                                                                     shall not penetrate floors, ceilings or roofs.
               1106.5.3 Emergency ventilation system discharge. The    Exceptions:
               emergency ventilation system point  of discharge  to the
               atmosphere shall be located outside of the structure at not  1. Penetrations connecting  the basement  and the
               less  than  15  feet (4572 mm) above the adjoining grade     first floor.
               level and not less than 20 feet (6096 mm) from any win-   2. Penetrations connecting the  top  floor and  a
               dow, ventilation opening or exit.                            machinery penthouse or roof installation.
             [F] 1106.6 Remote controls. Remote control of the mechani-  3. Penetrations connecting adjacent floors served by
             cal equipment and appliances located in the machinery room     the refrigeration system.
             shall comply with Sections 1106.6.1 and 1106.6.2.
                                                                         4. Penetrations by piping in a direct system where
               [F] 1106.6.1 Refrigeration system emergency shutoff. A       the refrigerant quantity does not exceed Table
               clearly identified switch of the break-glass type or with an  1103.1 for the smallest occupied space through
               approved tamper-resistant  cover shall provide  off-only     which the piping passes.
               control of refrigerant compressors, refrigerant pumps, and
               normally  closed, automatic refrigerant valves located in  5. In other than industrial occupancies and where
               the machinery room. Additionally, this equipment shall be    the refrigerant quantity exceeds Table 1103.1 for
               automatically shut off whenever the refrigerant vapor con-   the smallest space, penetrations for piping  that
               centration in the machinery room exceeds the vapor detec-    connects separate pieces of  equipment that are
               tor’s upper  detection  limit or 25 percent  of the LEL,     either:
               whichever is lower.                                             5.1. Enclosed by an  approved gas-tight,
               [F]  1106.6.2  Ventilation  system.  A clearly  identified          fire-resistive  duct or shaft with  open-
               switch of the break-glass type or with an approved tamper-          ings to those floors served by the refrig-
               resistant cover  shall provide on-only  control of the              eration system.
               machinery room ventilation fans.                                5.2. Located on the exterior of the building
             [F] 1106.7 Emergency signs and labels. Refrigeration units            where vented to the outdoors or to the
             and systems shall be  provided with  approved  emergency              space served by the system and not used
             signs, charts, and labels in accordance with the International        as an air shaft, closed court or similar
             Fire Code.                                                            space.
                                                                  1107.3 Pipe enclosures. Rigid or flexible metal enclosures or
                               SECTION 1107                       pipe ducts shall be provided for soft, annealed copper tubing
                           REFRIGERANT PIPING                     and used for refrigerant piping erected on the premises and
                                                                  containing other than Group A1  or B1 refrigerants. Enclo-
             1107.1 General. The design of refrigerant piping shall be in  sures shall not be required for connections between condens-
             accordance with ASME B31.5. Refrigerant  piping shall be  ing units and the nearest riser box(es), provided such
             installed, tested and placed in operation in accordance with  connections do not exceed 6 feet (1829 mm) in length.
             this chapter.
                                                                  1107.4  Condensation. Refrigerating piping and fittings,
                                                                  brine piping and fittings that, during normal operation, will