EXHAUST SYSTEMS



                               SECTION 505                        exhaust air rate. Such makeup air systems shall be equipped
                DOMESTIC COOKING EXHAUST EQUIPMENT                with a means of closure and shall be automatically controlled
             505.1  General. Domestic cooking exhaust equipment shall  to start and operate simultaneously with the exhaust system.
             comply with the requirements of this section.        505.5  Common  exhaust  systems  for  domestic  kitchens
             505.2 Domestic cooking exhaust. Where domestic cooking  located in multistory structures. Where a common multi-
             exhaust equipment is provided, it shall comply with the fol-  story duct system is designed and installed to convey exhaust
             lowing as applicable:                                from  multiple  domestic  kitchen exhaust systems, the con-
                                                                  struction of the system shall be in accordance with all of the
               1. The fan  for overhead range  hoods and downdraft  following:
                  exhaust equipment not integral with the cooking appli-
                  ance shall be listed and labeled in accordance with UL  1. The shaft in which the duct is installed shall be con-
                  507.                                                  structed and fire-resistance  rated as required by  the
                                                                        International Building Code.
               2. Overhead  range hoods and downdraft  exhaust  equip-
                  ment with integral fans shall comply with UL 507.   2. Dampers shall  be prohibited in the exhaust duct,
                                                                        except as specified in Section 505.3. Penetrations of
               3. Domestic cooking appliances with  integral downdraft  the  shaft and ductwork shall be protected in accor-
                  exhaust equipment shall be listed and labeled in accor-  dance with Section 607.5.5, Exception 2.
                  dance with UL 858 or ANSI Z21.1.
                                                                      3. Rigid metal ductwork shall be installed within  the
               4. Microwave ovens with integral exhaust for installation  shaft  to convey the exhaust. The ductwork shall  be
                  over the cooking surface shall be listed and labeled in  constructed of  sheet steel having a  minimum thick-
                  accordance with UL 923.
                                                                        ness of 0.0187 inch (0.4712 mm) (No. 26 gage) and in
             505.3 Exhaust ducts. Domestic cooking exhaust equipment    accordance with SMACNA Duct Construction Stand-
             shall discharge to the outdoors through sheet metal ducts con-  ards.
             structed of galvanized steel, stainless steel, aluminum or cop-  4. The ductwork within the shaft shall be designed and
             per. Such ducts shall have smooth inner walls, shall be air  installed without offsets.
             tight, shall be equipped with a backdraft damper, and shall be
             independent of all other exhaust systems. Installations in  5. The exhaust fan motor design shall be in accordance
             Group I-1 and I-2 occupancies shall be in accordance with the  with Section 503.2.
             International Building Code and Section 904.13 of the Inter-  6. The exhaust fan motor shall be located outside of the
             national Fire Code.                                        airstream.
               Exceptions:                                            7. The exhaust fan shall run continuously, and shall be
                                                                        connected to a standby power source.
                  1. In other than Groups I-1 and I-2, where installed in
                    accordance with the manufacturer’s instructions and  8. Exhaust fan operation shall be monitored in  an
                    where mechanical or natural ventilation is otherwise  approved location and shall initiate an  audible or
                    provided in accordance  with Chapter 4,  listed and  visual signal when the fan is not in operation.
                    labeled ductless range hoods shall not be required to  9. Where the exhaust  rate  for an individual kitchen
                                                                                             3
                    discharge to the outdoors.                          exceeds 400 cfm (0.19 m /s) makeup air shall be pro-
                  2. Ducts for domestic kitchen cooking  appliances     vided in accordance with Section 505.4.
                    equipped with  downdraft exhaust systems shall be  10. A cleanout opening shall be located at the base of the
                    permitted  to be constructed  of  Schedule 40 PVC   shaft to provide access to the duct to allow for clea-
                    pipe and fittings provided that the installation com-  nout and  inspection. The finished openings shall  be
                    plies with all of the following:                    not less than 12 inches by 12 inches (305 mm by 305
                                                                        mm).
                       2.1. The duct shall be installed under a concrete
                          slab poured on grade.                      11. Screens shall not be installed at the termination.
                       2.2. The underfloor trench in which the duct is  12. The common multistory duct system shall serve only
                          installed shall be completely backfilled with  kitchen exhaust and shall be independent of other
                          sand or gravel.                               exhaust systems.
                       2.3. The PVC duct shall extend not more than 1  505.6 Other than Group R. In other than Group R occupan-
                          inch  (25 mm) above  the indoor concrete  cies, where domestic cooktops, ranges, and open-top broilers
                          floor surface.                          are used for domestic purposes,  domestic cooking exhaust
                                                                  systems shall be provided.
                       2.4. The PVC duct shall extend not more than 1
                          inch (25  mm) above  grade outside of the
                          building.                                                 SECTION 506
                       2.5. The PVC ducts shall be solvent cemented.  COMMERCIAL KITCHEN HOOD VENTILATION
             505.4 Makeup air required. Exhaust hood systems capable  SYSTEM DUCTS AND EXHAUST EQUIPMENT
                                                 3
             of exhausting in excess of 400 cfm (0.19 m /s) shall be pro-  506.1 General. Commercial kitchen hood ventilation  ducts
             vided with makeup air at a rate approximately equal to the  and exhaust equipment shall comply with the requirements of