EXHAUST SYSTEMS




              fan components. Such rooms or spaces shall be venti-     water splash or carryover can occur in the transi-
              lated in accordance with the fan manufacturer’s instal-  tion  duct  as a  result of a  washing operation, the
              lation instructions.                                     transition  duct shall  slope downward toward  the
                                                                       cabinet drain pan  for  a length  not  less than 18
           506.5.2 Pollution-control units. The installation of pollu-
           tion-control units shall be in accordance with the manufac-  inches (457 mm). Ducts shall transition to the full
           turer’s installation instructions and all of the following:  size of the unit’s inlet and outlet openings.
                                                                   14. Extra-heavy-duty appliance exhaust systems shall
               1. Pollution-control units shall be listed and labeled
                  in accordance with UL 1978.                          not be connected to pollution-control units except
                                                                       where such  units are  specifically designed and
               2. Fans serving pollution-control units shall be listed  listed for use with solid fuels.
                  and labeled in accordance with UL 762.
                                                                   15. Pollution-control units  shall be maintained in
               3. Pollution-control units shall be mounted and         accordance with the manufacturer’s instructions.
                  secured  in accordance with the manufacturer’s
                  installation instructions and the  International  506.5.3  Exhaust  fan  discharge. Exhaust fans shall be
                  Building Code.                                 positioned so that the discharge will not impinge on the
                                                                 roof, other equipment or appliances or parts of the struc-
               4. Pollution-control units  located indoors shall be  ture. A vertical discharge fan shall be manufactured with
                  listed and labeled for such use. Where enclosed  an approved drain outlet at the lowest point of the housing
                  duct systems, as required by Section 506.3.11, are  to permit drainage of grease to an approved grease reser-
                  connected to a pollution  control unit, such unit  voir.
                  shall be located in a  room or space having the  506.5.4  Exhaust  fan  mounting. Up-blast fans serving
                  same fire-resistance rating as the duct enclosure.  Type I hoods and installed in a vertical or horizontal posi-
                  Access shall be provided for servicing and clean-  tion shall be hinged, supplied with a flexible weatherproof
                  ing of  the unit. The space or enclosure shall be  electrical cable to permit inspection and cleaning and shall
                  ventilated in accordance  with the manufacturer’s  be equipped with a means of restraint to limit the swing of
                  installation instructions.
                                                                 the fan on its hinge. The ductwork shall extend not less
               5. A clearance of not less than 18 inches (457 mm)  than 18 inches (457 mm) above the roof surface.
                  shall be maintained between the pollution-control  506.5.5 Clearances. Exhaust equipment serving a Type I
                  unit and combustible material.                 hood shall have a clearance to combustible construction of
               6. Roof-mounted pollution-control units shall be  not less than 18 inches (457 mm).
                  listed for outdoor installation and shall be mounted  Exception: Factory-built exhaust  equipment installed
                  not less than 18 inches (457 mm) above the roof.  in accordance with Section 304.1 and listed for a lesser
               7. Exhaust outlets for pollution-control units shall be  clearance.
                  in accordance with Section 506.3.13.           506.5.6  Termination  location. The outlet  of exhaust
               8. An airflow differential pressure control shall be  equipment serving Type  I hoods  shall be  in accordance
                  provided to monitor the pressure drop across the  with Section 506.3.13.
                  filter sections of a pollution-control unit. When the  Exception: The minimum horizontal distance between
                  airflow is reduced below the design velocity, the  vertical discharge fans and parapet-type building struc-
                  airflow differential pressure control shall activate  tures shall be 2 feet (610 mm) provided that such struc-
                  a visual alarm located in the area where cooking  tures are not higher than the top of the fan discharge
                  operations occur.                                opening.
               9. Pollution-control units shall be provided with a
                  factory-installed fire suppression system.
                                                                                SECTION 507
              10. Service space shall be provided in accordance with   COMMERCIAL KITCHEN HOODS
                  the manufacturer’s instructions for the pollution-
                  control unit and the requirements of Section 306.  507.1  General. Commercial kitchen exhaust hoods shall
                                                              comply with the requirements of this section. Hoods shall be
              11. Wash-down  drains shall discharge through a  Type I or II and shall  be designed to  capture and  confine
                  grease interceptor and shall be sized for the flow.  cooking vapors and residues. A Type I or Type II hood shall
                  Drains, shall be sealed with a trap or other  be installed at or above appliances in accordance with Sec-
                  approved means to prevent air bypass. Where  a  tions 507.2 and 507.3. Where any cooking appliance under a
                  trap is  utilized  it shall have a seal depth that  single hood requires a Type I hood, a Type I hood shall be
                  accounts for the system pressurization and evapo-  installed. Where a Type II hood is required, a Type I or Type
                  ration between cleanings.                   II hood shall be installed. Where a Type I hood is installed,
                                                              the installation of the entire system, including the hood,
              12. Protection from freezing shall be provided for the  ducts, exhaust equipment and makeup air system shall com-
                  water supply and fire suppression systems where  ply with the requirements of Sections 506, 507, 508 and 509.
                  such systems are subject to freezing.          Exceptions:
              13. Duct connections to pollution-control units shall  1. Factory-built commercial exhaust  hoods that are
                  be in accordance  with Section 506.3.2.3. Where    listed and labeled in accordance with UL 710, and


         56                                                                  2018 INTERNATIONAL MECHANICAL CODE 
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   68   69   70   71   72   73   74   75   76   77   78