Page 83 - 2018_IMC
P. 83

EXHAUST SYSTEMS




         [F] 513.10 Equipment. Equipment such as, but not limited  ments of the International Building Code. Motors driving
         to, fans, ducts, automatic dampers and balance dampers shall  fans shall not be operating beyond their nameplate horse-
         be suitable for their intended use, suitable for the probable  power  (kilowatts) as determined  from measurement  of
         exposure temperatures that the rational analysis indicates, and  actual current draw. Motors driving fans shall have a min-
         as approved by the code official.                       imum service factor of 1.15.
           [F] 513.10.1 Exhaust fans. Components of exhaust fans  [F] 513.11 Standby power. The smoke control system shall
           shall  be rated and certified  by  the manufacturer for the  be supplied with standby power in accordance with Section
           probable temperature rise to which the components will be  2702 of the International Building Code.
           exposed. This temperature rise shall be computed by:
                                                                 [F]  513.11.1  Equipment  room. The standby power
           T  = (Q /mc) + (T )                (Equation 5-3)     source and its transfer switches shall be in a room separate
                         a
             s
                 c
           where:                                                from the normal power transformers and switch gear and
                                                                 ventilated directly to and from the exterior. The room shall
           c = Specific heat of smoke at smoke-layer temperature,  be enclosed with not less than 1-hour fire-resistance-rated
                Btu/lb°F (kJ/kg • K).
                                                                 fire barriers constructed in accordance with Section 707 of
           m = Exhaust rate, pounds per second (kg/s).           the International Building Code or horizontal assemblies
           Q = Convective heat output of fire, Btu/s (kW).       constructed in accordance with Section 711 of the Interna-
             c
                                                                 tional Building Code, or both.
           T = Ambient temperature, °F (K).
             a
                                                                 [F] 513.11.2 Power sources and power surges. Elements
           T = Smoke temperature, °F (K).
             s
                                                                 of  the smoke  management system relying on volatile
              Exception:  Reduced  T  as calculated based on the
                                 s                               memories or the like shall be supplied with uninterruptible
              assurance of adequate dilution air.
                                                                 power sources of sufficient duration to span 15-minute pri-
           [F]  513.10.2  Ducts.  Duct materials and  joints shall be  mary power interruption. Elements of the smoke manage-
           capable of withstanding the probable temperatures and  ment system susceptible to power surges shall be suitably
           pressures to which they are exposed as determined  in  protected by conditioners, suppressors or other approved
           accordance with  Section 513.10.1. Ducts shall be con-  means.
           structed  and  supported in accordance with  Chapter  6.  [F]  513.12  Detection  and  control  systems.  Fire detection
           Ducts shall be leak tested  to  1.5 times  the  maximum  systems providing control input or output signals to mechani-
           design pressure in  accordance  with nationally  accepted  cal smoke control systems or elements thereof shall comply
           practices. Measured leakage shall not exceed 5 percent of  with the requirements of  Section 907 of the  International
           design flow. Results of such testing shall be a part of the  Building Code. Such systems shall be equipped with a control
           documentation procedure.  Ducts  shall be supported  unit complying with  UL  864 and  listed as  smoke control
           directly from  fire-resistance-rated structural elements  of  equipment.
           the building by substantial, noncombustible supports.
                                                                 [F] 513.12.1 Verification. Control systems for mechani-
              Exception:  Flexible connections,  for the purpose  of
              vibration isolation, that are constructed of  approved  cal smoke control systems shall include provisions for ver-
              fire-resistance-rated materials.                   ification. Verification shall include positive confirmation
           [F] 513.10.3 Equipment, inlets and outlets. Equipment  of actuation, testing, manual override and the presence of
                                                                 power downstream of all disconnects. A preprogrammed
           shall be located so as to not expose uninvolved portions of  weekly test  sequence shall report abnormal conditions
           the building to an additional fire hazard. Outdoor air inlets  audibly, visually  and by printed  report. The  prepro-
           shall be located so as to minimize the potential for intro-  grammed weekly test shall operate all devices, equipment
           ducing smoke or flame into the building. Exhaust outlets  and components used for smoke control.
           shall be so located as to minimize reintroduction of smoke
           into the building and to limit exposure of the building or  Exception: Where  verification of individual compo-
           adjacent buildings to an additional fire hazard.        nents tested through the preprogrammed weekly testing
                                                                   sequence will interfere with, and produce unwanted
           [F]  513.10.4  Automatic  dampers.  Automatic dampers,  effects to, normal building operation, such individual
           regardless of the  purpose for  which they are installed  components are permitted to be bypassed from the pre-
           within the smoke control system, shall be listed and con-  programmed weekly testing,  where  approved by the
           form to the  requirements  of  approved  recognized stan-  building official and in accordance with both of the fol-
           dards.
                                                                   lowing:
           [F] 513.10.5 Fans. In addition to other requirements, belt-
           driven fans shall have  1.5 times  the  number of belts   1. Where the operation of components is bypassed
           required for the design duty with the minimum number of      from the preprogrammed weekly test, presence of
           belts being two. Fans shall be selected for stable perfor-   power  downstream  of all disconnects shall be
           mance based on normal temperature and, where applica-        verified weekly by a listed control unit.
           ble, elevated temperature. Calculations and manufacturer’s  2. Testing of all components bypassed from the pre-
           fan curves shall be part of the documentation procedures.    programmed weekly test shall be in accordance
           Fans shall be supported and restrained by noncombustible     with Section 909.20.6 of  the  International  Fire
           devices in accordance with the structural design require-    Code.

         66                                                                  2018 INTERNATIONAL MECHANICAL CODE 
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   78   79   80   81   82   83   84   85   86   87   88