Page 86 - 2018_IMC
P. 86

CHAPTER 6

                                                    DUCT SYSTEMS




             User note:
                About this chapter: Chapter 6 addresses duct systems used in HVAC systems and some exhaust systems. Some exhaust system ducts are
                addressed in Chapter 5, such as kitchen exhaust ducts and clothes dryer exhaust ducts. This chapter addresses air plenums such as above-ceil-
                                                                                                                  ®
                ing and below-floor plenums. Section 607 covers fire and smoke dampers, consistent with the requirements of the International Building Code .


                               SECTION 601                             4. The air-handling system serving the corridor is shut
                                 GENERAL                                 down upon detection of sprinkler waterflow where
                                                                         the building is equipped throughout with an auto-
             601.1 Scope. Duct systems used for the movement of air in
             air-conditioning, heating,  ventilating and exhaust  systems  matic sprinkler system.
             shall conform to the provisions of this chapter except as oth-  5. The space between the corridor ceiling and the floor
             erwise specified in Chapters 5 and 7.                       or roof structure above the corridor is used as a com-
                                                                         ponent of an  approved engineered  smoke control
               Exception: Ducts discharging  combustible  material
               directly into any combustion chamber shall conform to the  system.
               requirements of NFPA 82.                           [BE] 601.3 Exits. Equipment and ductwork for exit enclosure
                                                                  ventilation shall comply with one of the following items:
             [BE]  601.2  Air  movement  in  egress  elements.  Corridors
             shall not serve as supply, return, exhaust, relief or ventilation  1. Such equipment and ductwork shall be located exterior
             air ducts.                                                to the building and shall be directly connected to the
               Exceptions:                                             exit enclosure by ductwork enclosed in construction as
                                                                       required by the International Building Code for shafts.
                  1. Use of a corridor  as a source of  makeup  air for  2. Where such equipment and ductwork is located within
                    exhaust systems in  rooms that  open directly  onto  the exit enclosure, the intake air shall be taken directly
                    such corridors, including  toilet  rooms, bathrooms,  from the outdoors  and the  exhaust  air shall be dis-
                    dressing rooms, smoking lounges and janitor clos-  charged directly  to the outdoors, or such air shall be
                    ets, shall be permitted, provided that each such cor-  conveyed through ducts enclosed in construction as
                    ridor is directly supplied with outdoor air at a rate  required by the International Building Code for shafts.
                    greater than the rate of makeup air taken from the
                    corridor.                                        3. Where located within the building, such equipment and
                                                                       ductwork shall be separated from the remainder of the
                  2. Where located within a dwelling unit, the use of cor-
                    ridors for conveying return air shall not be prohib-  building, including  other mechanical  equipment, with
                                                                       construction as required by the International Building
                    ited.
                                                                       Code for shafts.
                  3. Where located within tenant spaces of 1,000 square  In each case, openings into fire-resistance-rated construc-
                             2
                    feet (93 m ) or less in area, use of corridors for con-  tion shall be limited to those needed for maintenance and
                    veying return air is permitted.
                                                                  operation and shall be  protected  by self-closing fire-resis-
                  4. Incidental air  movement  from pressurized rooms  tance-rated devices in accordance  with the  International
                    within health care facilities, provided that the corri-  Building  Code for  enclosure wall opening  protectives. Exit
                    dor is not the primary source of supply or return to  enclosure ventilation systems shall be independent of other
                    the room.                                     building ventilation systems.
               [BE] 601.2.1 Corridor ceiling. Use of the space between  601.4 Contamination prevention. Exhaust ducts under posi-
               the corridor ceiling and the floor or roof structure above as  tive  pressure, chimneys  and vents shall not  extend into or
               a return air plenum is permitted for one or more of the fol-  pass through ducts or plenums.
               lowing conditions:                                    Exceptions:
                  1. The corridor is not required to be of fire-resistance-  1. Exhaust  systems located in ceiling  return  air ple-
                    rated construction.
                                                                         nums over spaces that are permitted to have 10 per-
                  2. The corridor is separated from the plenum by fire-  cent recirculation  in accordance with  Section
                    resistance-rated construction.                       403.2.1, Item 4. The exhaust duct joints, seams and
                  3. The air-handling system serving the corridor is shut  connections shall comply with Section 603.9.
                    down upon activation of the air-handling unit smoke  2. This section shall not apply to chimneys and vents
                    detectors required by this code.                     that pass through plenums where such venting sys-



             2018 INTERNATIONAL MECHANICAL CODE                                                                  69
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   81   82   83   84   85   86   87   88   89   90   91