DUCT SYSTEMS




         602.3 Stud cavity and joist space plenums. Stud wall cavi-             SECTION 603
         ties and the spaces between solid floor joists to be utilized as  DUCT CONSTRUCTION AND INSTALLATION
         air plenums shall comply with the following conditions:  603.1 General. An air distribution system shall be designed
           1. Such cavities or spaces shall not be utilized as a plenum  and installed to supply the required distribution of air. The
              for supply air.                                 installation of an air distribution system shall not affect the
                                                              fire protection requirements  specified  in the  International
           2. Such cavities or spaces shall not be part of a required
              fire-resistance-rated assembly.                 Building Code. Ducts shall be constructed, braced, reinforced
                                                              and installed to provide structural strength and durability.
           3. Stud wall cavities shall not convey air from more than
              one floor level.                                603.2 Duct sizing. Ducts installed within a single dwelling
                                                              unit shall be sized in accordance with ACCA Manual D, the
           4. Stud wall cavities and joist space plenums shall comply  appliance  manufacturer’s installation instructions or other
              with the floor penetration  protection requirements of  approved methods. Ducts installed within all other buildings
              the International Building Code.                shall be sized in accordance with the ASHRAE Handbook of
           5. Stud wall cavities and joist space plenums shall be iso-  Fundamentals or other equivalent computation procedure.
              lated from adjacent concealed spaces by approved fire-  603.3 Duct classification. Ducts shall be classified based on
              blocking as required in the  International  Building  the maximum operating pressure of the duct at pressures of
              Code.                                           positive or negative 0.5, 1.0, 2.0, 3.0, 4.0, 6.0 or 10.0 inches
           6. Stud wall cavities in the outside walls of building enve-  (1 inch w.c. = 248.7 Pa) of water column. The pressure classi-
              lope assemblies shall not be utilized as air plenums.  fication of ducts shall equal or exceed the design pressure of
                                                              the air distribution in which the ducts are utilized.
         [BS]  602.4  Flood  hazard. For structures located in flood
         hazard areas, plenum spaces shall be located above the eleva-  603.4 Metallic ducts. Metallic ducts shall be constructed as
         tion required by Section 1612 of the International Building  specified in the SMACNA  HVAC  Duct  Construction Stan-
         Code for  utilities and attendant equipment or shall be  dards—Metal and Flexible.
         designed and constructed to prevent water from entering or  Exception: Ducts installed within single  dwelling  units
         accumulating within the plenum spaces during floods up to  shall  have  a minimum  thickness as specified in  Table
         such elevation.  If the plenum spaces are located below the  603.4.
         elevation required by  Section 1612 of the  International  603.4.1 Minimum fasteners. Round metallic ducts shall
         Building  Code  for  utilities and attendant equipment, they  be mechanically fastened by means of not less than three
         shall be capable of resisting hydrostatic and hydrodynamic  sheet metal  screws  or  rivets spaced equally around  the
         loads and stresses, including the effects of buoyancy, during  joint.
         the occurrence of flooding up to such elevation.
                                                                   Exception: Where a  duct connection is  made that  is
                                                                   partially inaccessible, three screws or rivets shall be

                                                       TABLE 603.4
                        DUCT CONSTRUCTION MINIMUM SHEET METAL THICKNESS FOR SINGLE DWELLING UNITS a
                                                                  STATIC PRESSURE
                                               1 / 2 -inch water gauge                1-inch water gauge
             ROUND DUCT DIAMETER                Thickness (inches)                    Thickness (inches)
                   (inches)              Galvanized         Aluminum           Galvanized         Aluminum
         < 12                             0.013              0.018              0.013               0.018
         12 to14                          0.013              0.018              0.016               0.023
         15 to 17                         0.016              0.023              0.019               0.027
         18                               0.016              0.023              0.024               0.034
         19 to 20                         0.019              0.027              0.024               0.034
                                                                  STATIC PRESSURE
                                               1 / 2 -inch water gauge                1-inch water gauge
          RECTANGULAR DUCT DIMENSION            Thickness (inches)                    Thickness (inches)
                   (inches)              Galvanized         Aluminum           Galvanized         Aluminum
         ≤ 8                              0.013              0.018              0.013               0.018
         9 to10                           0.013              0.018              0.016               0.023
         11 to 12                         0.016              0.023              0.019               0.027
         13 to 16                         0.019              0.027              0.019               0.027
         17 to 18                         0.019              0.027              0.024               0.034
         19 to 20                         0.024              0.034              0.024               0.034
         For SI: 1 inch = 25.4 mm, 1-inch water gauge = 249 Pa.
         a. Ductwork that exceeds 20 inches by dimension or exceeds a pressure of 1-inch water gauge shall be constructed in accordance with SMACNA HVAC Duct
           Construction Standards—Metal and Flexible.